Settings
29
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
4.2.1
Configurable Inputs
These inputs are used to create custom warnings and failures. Using the RapidCore Configuration Software you can change the
text displayed when the warning or failure occurs. If you select one of these inputs without changing the text it will default to 'Config
Warn X' and 'Config Fail X.'
There are also timers associated with the configurable inputs which can be found in the menu under
Timers > Trigger Delays >
Config Inputs and Config Fail 3
. These timers change the amount of time the input has to be active before the controller registers
the warning or failure.
NOTE
: If the switched input becomes inactive before the trigger delay time expires, the warning or failure will not
occur.
Example:
The user wants a pump to turn on 30 seconds after a high water level switch is tripped and remain on until the level
switch turns off.
The level switch is connected to Switched Input C and closes to ground when the water level is too high. The words 'Water
Pumping' are also required to be displayed on the controllers LCD screen. The pump is connected to a slave relay which is
controlled by Switched Output D on the controller.
Relevant Settings
Setting
Value
Switched Input C -> Function
Configurable Warning 1
Switched Input C -> Active Mode
Global
Switched Input C -> Trigger
Close GND
Configurable Warning 1 Custom Text
Water Pumping
Switched Output D -> Warnings
Configurable Warning 1
4.3
Switched Outputs
The controller has switched outputs that are turned on under certain conditions to perform a function. The outputs turn on to
+Battery voltage to drive the load when active. The following items are the available functions for switched outputs.
WARNING
: Switched outputs have a floating voltage of approximately 8V when off. If using the outputs for digital logic,
it will be necessary to put a pull-down resistor (1 kOhm) from the output to ground to ensure a low logic level when
output is off.
Event Functions
Name
Active Mode
Description
Fuel
Cranking, Running
Active during cranking and running to supply fuel to engine.
Crank
Cranking
Active during cranking to start the engine.
Pull Coil
Cranking
See
section for more information.
LCD Backlight
Global
Active when LCD Backlight is active.
Voltage Regulator
Running
Active when engine is starting/running and is not in Idle Mode.
ETS (Energize to Stop)
ETS Timer
Active during Energize to Stop timer.
Off Mode (Not In Auto)
Off
Active when the controller is in the OFF mode.
Idle Mode
Idle Mode
Active when Idle Mode switched input is active.
Battle Mode
Battle Mode
Active when Battle Mode switched input is active.
System OK (System
Ready)
Auto, Run
Active when the controller is in the AUTO and RUN mode and no warnings or
failures are present.
Delay to Start
Delay to Start Timer
Active when the Delay to Start timer is active.
Glowplug
Preheat, Midheat,
Postheat
Active during the Preheat, Midheat and Postheat timers.
Summary of Contents for TG410
Page 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...