29
[06]
Second System Options
1 [F] Key Disable / Enable
ON:
[F] Key Disabled.
The [F] Key is disabled and will not function when pressed.
•
OFF:
[F] Key Enabled.
When pressed and held for 2 seconds, a Fire Alarm will be
generated. An [F] Key alarm reporting code, if programmed, will be transmitted to
the monitoring station and the Sounders will sound.
2 [P] Key Disable / Enable
ON:
[P] Key Disabled.
The [P] Key is disabled and will not function when pressed.
•
OFF:
[P] Key Enabled.
When pressed and held for 2 seconds, an Alarm will be
generated. A [P] Key alarm reporting code, if programmed, will be transmitted to
the monitoring station and the Sounders will sound if programmed to do so.
3 [A] Key Disable / Enable
ON:
[A] Key Disabled.
The [A] Key is disabled and will not function when pressed.
•
OFF:
[A] Key Enabled.
When pressed and held for 2 seconds, an Auxiliary Alarm will be
generated. An [A] Key alarm reporting code, if programmed, will be transmitted to
the monitoring station. The [A] Key alarm is silent; when the [A] Key is pressed, the
Sounders will not sound. When the [A] Key alarm has been reported to the
monitoring station, the Sounders will sound several beeps to acknowledge completion
of the transmission.
4 [P] Key Audible / Silent
ON:
[P] Key Audible.
When the [P] Key is pressed and held for 2 seconds, the
Sounders will be activated.
•
OFF:
[P] Key Silent.
When the [P] Key is pressed and held for 2 seconds, the
Sounders will not be activated.
5 [F] Key Alarm Steady / Pulsed
ON
:
[F] Key Alarm Sounds Steady Beep.
When an [F] key alarm is generated, the
Sounders will sound with a loud, steady alarm sound.
•
OFF:
[F] Key Alarm Sounds with Pulsed Beep.
When an [F] Key Alarm is generated,
the Sounders will sound with a loud, pulsing alarm sound.
6 Bypassing Disable / Enable
ON:
Bypassing Disabled.
Users will not be able to manually bypass zones.
•
OFF:
Bypassing Enabled.
Users will be able to manually bypass all zones other than
Fire Zones.
7 Keypad Lockout Enable / Disable
ON:
Keypad Lockout Enabled.
After four incorrect Access Codes have been entered on
the Keypad, the system will not accept further entries on the Keypad for 45 seconds;
even valid Access Codes will not be accepted.
•
OFF:Keypad Lockout Disabled.
The Keypad will not lock out regardless of the number
of incorrect entries made.
8 AC Frequency
ON:
AC Frequency at 50Hz.
Use for most European installations.
•
OFF:
AC Frequency at 60Hz.
Use for North American installations.
•
Indicates default setting