25
XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Steam outlet connections with hose
INSTALLATION
Dispersion:
1½" (DN40) hose connections
from two cylinders
2" (DN50) steam hose connection
3" (DN80) fl ange connection
2" (DN50) hose connections
from two cylinders
OM-7913
OM-7914
Notes:
• For two cylinders, connect the stainless steel tube connector directly to the dispersion inlet as shown.
The diameter and pitch of the tube connector must match the inlet diameter and pitch of the dispersion unit.
•
Always run separate steam hose/tubing from each cylinder to the connection of the dispersion device.
Only connect a maximum of two cylinders to any single dispersion unit.
FIGURE 25-1: CONNECTING TWO CYLINDERS TO A DISPERSION ASSEMBLY
WARNING
Preventing back pressure/abnormal
operation in dual cylinder humidifi ers
and installations where two individual
units are connected to a single
dispersion panel.
Read and follow all steam hose
installation instructions. Failure to
follow these instructions could result in
excessive back pressure or abnormal
operation of the unit. Severe personal
injury or damage to the unit may result.