background image

7

XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

The duct dispersion options in Figure 7-1 and the open space dispersion 
options in Figure 7-2 are available for XT Series humidifi ers. For 
installation details, see “Dispersion” beginning on Page 20.

 Dispersion options 

SPECIFICATIONS

Ultra-sorb

Rapid-sorb

Single dispersion tube

Notes:  
•  Models XTP 010 and larger require condensate drain. See Page 32.
•  XT steam blowers (SDU) shipped with fuses to be installed in connected XT series humidifi ers.

OM-7667

OM-7669

OM-7668

Mounted on top of humidifi er

Mounted up to 10' (3 m) away from 
humidifi er

OM-7670

OM-7698

FIGURE 7-2:   XT STEAM BLOWERS

FIGURE 7-1:   XT SERIES HUMIDIFIER DUCT DISPERSION OPTIONS 

Summary of Contents for XT Series

Page 1: ...XT SERIES Electrode Steam Humidifiers Installation Operation and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS ...

Page 2: ... dispersion assemblies can be as hot as 212 F 100 C Discharged steam is not visible Contact with hot surfaces discharged hot water or air into which steam has been discharged can cause severe personal injury To avoid severe burns follow the cool down procedure in this manual before performing service or maintenance procedures on any part of the system Disconnect electrical power Disconnect electri...

Page 3: ... as 212 F 100 C and can damage some drain plumbing materials not rated for hot drain water To prevent such damage make sure drain water tempering is selected and supply water is not heated Do not shut off supply water to the cylinder before it is drained Excessive supply water pressure Supply water pressure greater than 80 psi 550 kPa can cause the humidifier to overflow WARNING Electrical shock haz...

Page 4: ...e dispersion assembly location 20 Returning condensate to steam cylinder 22 Steam outlet connections 23 Steam outlet connections with hose 24 Single dispersion tube 28 Drip tee installation 31 Connecting to humidifier with tubing 32 Rapid sorb 33 XT steam blowers 40 Principle of operation 45 ATTENTION INSTALLER Original Instructions Read this manual before installing Leave manual with product owne...

Page 5: ...NTENANCE MANUAL Table of contents OPERATION 45 Start up checklist 47 Model XTP 48 Shutdown and cool down procedures 49 MAINTENANCE 49 Replacing steam cylinder 50 Drain valve 51 Troubleshooting 52 Replacement parts 56 Accessories 61 WARRANTY 64 ...

Page 6: ... electrical resistance in their fill water to boil the fill water into humidification steam Steam output and water conductivity are managed via automatic draining and filling See Figure 2 1 Steam to duct or XT steam blower see dispersion options on Page 8 Electrodes Electrical resistance in fill water Overflow to drain Supply water connection Control panel for on board controller see Figure 3 1 Steam cy...

Page 7: ...oftened water can reduce scale build up in the cylinder it can also shorten cylinder electrode life CONTROLLER The Model XTP humidifier Vapor logic controller features menus for all humidifier functions with a Web interface for access to all functions via Ethernet See Operations beginning on page 45 for details On off switch for control board not a safety shut off to humidifier power wiring XTP Vapor...

Page 8: ...25 240 17 25 400 10 13 480 9 15 600 7 10 010 30 14 10 0 3 208 33 45 240 29 40 400 17 25 480 14 20 600 12 15 017 50 22 16 5 3 208 55 70 240 48 60 400 29 40 480 24 35 600 19 25 025 75 34 25 0 3 400 43 63 480 36 50 600 29 40 033 100 45 33 3 3 400 58 80 480 48 70 600 39 50 042 125 57 41 7 3 400 72 100 480 60 80 600 48 70 048 143 65 47 8 3 400 80 100 480 69 90 600 55 70 050 150 68 50 0 3 400 2 x 43 2 x...

Page 9: ...mensions in Figure 9 1 Models XTP 002 through 048 E D Electrical knockout Top Bottom Front Drain outlet Electrical knockouts Supply water connection B OM 7672 10 0 254 Fill cup extension kit OM 7673 D B E F Models XTP 050 through 096 10 0 254 21 0 533 Dispersion outlets Drain outlets Supply water connections Fill cup extension kits A A C C F Front Top Bottom Electrical knockout Dispersion outlet E...

Page 10: ... edge to steam drain outlet centers 4 5 114 6 0 152 6 7 170 6 7 170 E Cabinet left edge to steam drain outlet centers 4 4 112 6 0 152 7 0 178 7 0 178 F Cabinet back edge to supply water connection center 6 7 170 9 5 241 11 1 282 11 1 282 G Cabinet left edge to supply water connection center 1 0 25 1 0 25 1 1 28 1 1 28 Table 6 2 XT Series humidifier weights by model number Model XTP 002 003 006 010...

Page 11: ... on Page 20 Dispersion options SPECIFICATIONS Ultra sorb Rapid sorb Single dispersion tube Notes Models XTP 010 and larger require condensate drain See Page 32 XT steam blowers SDU shipped with fuses to be installed in connected XT series humidifiers OM 7667 OM 7669 OM 7668 Mounted on top of humidifier Mounted up to 10 3 m away from humidifier OM 7670 OM 7698 FIGURE 7 2 XT STEAM BLOWERS FIGURE 7 1 XT...

Page 12: ...y RH Install humidifier only in locations that meet the following temperature and RH requirements Maximum ambient temperature 104 F 40 C Minimum ambient temperature 41 F 5 C Maximum ambient humidity 80 RH non condensing Required clearances see Figure 8 1 Electrical connections Electrical power supply connections are at the lower or upper right rear corner of the unit See Humidifier wiring on Pages 1...

Page 13: ... 003 006 010 017 025 033 042 048 050 067 083 096 inches mm inches mm inches mm inches mm A 3 9 100 7 1 180 7 5 190 14 0 356 B 3 0 75 3 6 92 3 4 86 3 3 84 C 3 2 81 4 4 112 4 1 104 4 1 104 D 14 0 355 16 3 414 18 9 480 18 9 480 E 19 0 483 INSTALLATION E 0 390 x 0 719 9 9 x 18 3 mm dia keyholes 0 390 9 9 mm dia holes 0 390 x 0 719 9 9 x 18 3 mm dia keyholes 0 390 9 9 mm dia holes FIGURE 9 1 XT SERIES ...

Page 14: ...oth sides of drain outlet 4 Press up against bottom of cylinder with backs of hands while pressing down against cabinet floor with fingers 5 Raise cylinder until drain outlet clears drain valve body and the side tabs on the cylinder have cleared the cylinder guides Remove cylinder from cabinet WALL MOUNTING HUMIDIFIER Mount the humidifier level and plumb using the lag bolts provided Follow the inst...

Page 15: ...of XT cabinet INSTALLING FILL CUP EXTENSION KIT 1 Remove steam cylinder s from XT cabinet if not already out 2 Route fill cup extension kit hoses into cabinet through fill cup hole and fasten extension bracket as shown with two screws provided 3 Route hoses along back of cabinet interior to provide clearance for cylinder 4 Cut supply water hose small diameter hose A to length so it can attach to f...

Page 16: ...r cylinder drain outlet into drain valve body and rotate cylinder so side tabs line up with cylinder guides inside cabinet Push down on cylinder until drain outlet is fully seated in drain valve body 6 Slide steam hose down so it is fully engaged on cylinder steam outlet Re install hose clamp s 7 Connect high water sensor yellow wire to single pin surrounded by plastic shoulder on cylinder 8 Conne...

Page 17: ...tures user selectable drain water tempering When drain water tempering is selected the humidifier tempers drain water by opening the fill valve whenever the drain valve is energized to cool drain water before it enters the drain Drain water tempering keeps water entering the drain line less than 140 F 60 C Manually energizing the drain valve when the supply water is shut off can allow 212 F 100 C wa...

Page 18: ... and maximum discharge water temperature Install spill funnels plumb to floor drain Metallic water supply line 3 8 DN10 copper water supply line water pressure must be 25 to 80 psi 175 to 550 kPa Fill valve with 1 4 FIP 3 8 BSP DN10 in Europe supply water connection 1 DN32 drain piping after second drain connection or if piping run is over 10 3 m 1 25 mm air gap required to isolate unit drain pipin...

Page 19: ...ween humidifier and XT steam blower is 10 3 m Models XTP 042 through 096 are not intended for use with a steam blower OM 7975 7 178 mm water seal To open drain or humidifier fill cup Water seal is required whether condensate is piped to open drain or returned to humidifier fill cup Plastic tie Condensate hose purchased separately from DriSteem Hose clamps provided Steam hose purchased separately from D...

Page 20: ...6 Notes Maximum recommended distance between humidifier and XT steam blower is 10 3 m Models XTP 025 and 033 are not intended for use with a direct mounted steam blower Models XTP 042 through 096 are not intended for use with a steam blower Piping XT steam blowers FIGURE 16 1 PIPING FROM XT SERIES HUMIDIFIER TO TOP MOUNTED XT STEAM BLOWER ...

Page 21: ...tect all internal components from debris and vacuum out the cabinet when finished Failure to follow these precautions can damage sensitive electronic components and void the DriSteem warranty Notes Control wiring and power wiring must be run in dedicated or separate earthed metal conduit cable trays or trunking Separate the line voltage wiring from low voltage control circuit wiring when routing el...

Page 22: ...e power to the steam blower Fuses are shipped with the steam blower Replacements available from DriSteem WARNING Excessive moisture hazard DriSteem strongly recommends installing a duct airflow proving switch and a duct high limit humidistat These devices prevent a humidifier from making steam when there is low airflow in the duct or when the RH level in the duct is too high Failure to install these ...

Page 23: ... control B Acceptable but room environment can affect controllability such as when sensor is too close to air grilles registers or heat radiation from room lighting C Acceptable Provides uniform mixture of dry and moist air If extended time lag exists between humidity generation and sensing extend sampling time D Acceptable behind wall or partition for sampling entire room if sensor is near an air...

Page 24: ...r handling units must be positioned where the water vapor being discharged is carried off with the airstream and is absorbed before it can cause condensation or dripping In general the dispersion assembly is best placed where the air can absorb the moisture being added without causing condensation at or after the unit This normally will be after the heating coil or where the air temperature is hig...

Page 25: ...t more moisture into one duct than the other When draining dispersion condensate to an open drain provide a 1 25 mm air gap between the condensate drain piping and the drain Locate the gap only in spaces with adequate temperature and air movement to absorb flash steam otherwise condensation may form on nearby surfaces WARNING Hot surface and steam hazard Dispersion assembly and steam hose or tubing...

Page 26: ...ed installation shown in Figure 29 1 Dispersion CONDENSATE RETURN GUIDELINES To prevent overfilling the steam cylinder follow the condensate guidelines below When condensate can be returned to the steam cylinder Single dispersion tube Up to 20 lbs hr 9 1 kg h of steam production 10 3 m or less of steam hose between humidifier and dispersion 20 6 m or less of tubing between humidifier and dispersion W...

Page 27: ...se clamp optional Provided in optional connector kit Part No 191070 100 see Table 61 1 Provided by installer CAUTION Connector kit location Install the connector for increasing from 1 to 1 DN25 to DN40 hose or tube immediately above the XT Series humidifier as shown above Failure to install the connector kit immediately above the humidifier will cause system pressure fluctuations and increase cylinde...

Page 28: ...vided in optional connector kit Part No 191070 002 Provided in optional connector kit Part No 162825 202F FIGURE 24 1 STEAM OUTLET CONNECTIONS WITH HOSE MODELS XTP 033 THROUGH XTP096 WITHIN 10 3 M OF DISPERSION ASSEMBLY Dispersion 2 DN50 steam hose 10 3 m maximum Stainless steel Y connector Hose clamp OM 7981 OM 7979 Models XTP 033 042 and 048 1 DN40 steam hose 12 305 mm long Model XTP 050 OM 7980...

Page 29: ... and pitch of the dispersion unit Always run separate steam hose tubing from each cylinder to the connection of the dispersion device Only connect a maximum of two cylinders to any single dispersion unit FIGURE 25 1 CONNECTING TWO CYLINDERS TO A DISPERSION ASSEMBLY WARNING Preventing back pressure abnormal operation in dual cylinder humidifiers and installations where two individual units are conn...

Page 30: ...ults Field supplied hose may have shorter life and may cause foaming in cylinder resulting in condensate discharge at dispersion assembly Do not use steam hose for outdoor applications These models have two steam cylinders Capacities based on use with fill cup extensions For Models XTP 050 through XTP 096 capacities listed are maximum steam carrying capacity per tube attached to each cylinder with ...

Page 31: ... 15 toward the steam cylinder For dispersion devices with condensate drain maintain a minimum pitch of 2 ft 15 toward the dispersion device Use DriSteem steam hose Other manufacturers of steam hose may use unacceptable release agents or material mixes that can affect humidifier system performance adversely Using hose from alternative manufacturers increases the possibility of foaming in the cylinde...

Page 32: ...0 long sweeps Two 45 elbows 1 0 3 m apart may also be used Insulating tubing reduces the loss in output caused by condensation If flux or any other surface preparation material is used when connecting steam tubing and fittings drain and fill the steam cylinder two times after the first half hour of steam production Model XTP step 5 on page 48 This will minimize the possibility of foaming in the steam ...

Page 33: ...mended 8 200 mm minimum 1 25 mm air gap Open funnel or floor drain See first note below 3 4 DN20 Tubing drip tee by installer see Part No in Table 61 1 Pitch XT Series humidifier Notes Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam otherwise condensation may form on nearby surfaces Refer to governing codes for drain pipe size and maximum discharge water ...

Page 34: ...tuations and increase cylinder pressure steam velocity and condensate noise DISPERSION TUBE WITH OR WITHOUT CONDENSATE DRAIN Use a hose cuff and clamps to connect the steam outlet to tubing Tubing diameter must match XT steam outlet connection See maximum steam carrying capacities in Table 26 1 and steam loss in Table 27 1 If mounting the humidifier above the level of dispersion tube see Drip tee i...

Page 35: ...rovided by installer 90 long sweep or two 45 elbows Mounting nut 3 8 16 M10 Duct Secure and seal escutcheon plates Dispersion tube Orient with tubelets steam orifices pointing up Pitch steam hose or tubing toward humidifier 2 ft 15 when using steam hose ft 5 when using 1 tubing ft 2 when using 2 tubing 4 5 115 mm minimum from top of duct Tubing must be grounded Insulate tubing to reduce steam loss S...

Page 36: ...ose dispersion tube and hardware Maximum tube capacity Insulated Uninsulated lbs hr kg h lbs hr kg h 1 DN40 without drain 29 0 13 2 28 0 12 7 1 DN40 with drain 65 0 29 5 62 0 28 1 These capacities require multiple tube assemblies and cannot use a single hose kit 65 0 29 5 62 0 28 1 Capacities of Models XTP 025 through XTP096 require multiple tube assemblies and cannot use a hose kit For multiple t...

Page 37: ...l mounting hole in the center Note Hardware for mounting the L bracket to the duct or air handler wall and the hardware for the header support bracket is not provided Select an installation location that provides necessary access in and around the ductwork or air handler The Rapid sorb typically is installed centered side to side in a duct or is installed across the face of a coil in an air handle...

Page 38: ...duct consider the following 1 DN40 dispersion tubes Use a fastener of sufficient length to accommodate the 1 8 ft 1 pitch requirement toward the 3 4 pipe thread DN20 header drain fitting 2 DN50 dispersion tubes Bracket can be mounted flush to ductwork Typically the 1 8 ft 1 pitch can be accomplished in the length of the hose cuffs used to connect tubes to header See Table 34 3 and the drawings on the...

Page 39: ...e temperature and air movement to absorb flash steam otherwise condensation may form on nearby surfaces Refer to governing codes for drain pipe size and maximum discharge water temperature Tubing must be grounded Insulate tubing to reduce steam loss See Tables 26 1 and 27 1 for maximum tubing lengths See Notes L bracket Install with flange facing upstream direction of airflow Drawing shows L bracket ...

Page 40: ...n order to eliminate a condensate collection point that will restrict steam flow OM 7982 XT Pitch Pitch Drain Drain Drip tee Pitch Pitch Drain Rapid sorb steam dispersion panel Ultra sorb steam dispersion panel Dual cylinder XT Series humidifier WARNING Preventing back pressure in dual cylinder humidifiers Read and follow all steam tubing installation instructions for dual cylinder humidifiers Failur...

Page 41: ... for 1 DN40 dispersion tubes take care not to shear O rings Set slip coupling on header stub or dispersion tube so O ring is resting on face of tubing Rotate slip coupling while pushing it onto the tubing O rings are lubricated at factory If additional lubrication is necessary DO NOT use petroleum based lubricant 5 Allow the dispersion tubes to rest against the bottom of the duct CAUTION Operate R...

Page 42: ...n be fastened tight to duct or air handler Fastener on low end of L bracket must be long enough to compensate for pitch Use a nut on both sides of L bracket and duct or air handler for stability 2 DN50 dispersion tubes Fasten bracket to top of duct and use hose cuffs to compensate for header pitch Before securing hose cuffs with hose clamps on dispersion tube and header stub verify that dispersion...

Page 43: ...e maintaining the necessary pitch 3 Make sure the hose clamps on the steam supply connector and header are tight CONDENSATE DRAIN CONNECTIONS TO RAPID SORB HEADER Piping must be minimum 3 4 I D DN20 and rated for 212 F 100 C minimum continuous operating temperature The condensate drain line must be piped as shown in Figure 35 1 Provide a 6 150 mm drop prior to a 5 125 mm water seal to Ensure drain...

Page 44: ... outlet of the XT steam blower Throw Minimum non wetting horizontal distance from the steam outlet of the XT steam blower These models use two XT steam blowers Fuses provided with the steam blowers must first be installed in the associated XT series humidifiers On a call for humidity the controller closes the contactors to energize the humidifier electrodes and the XT steam blower When the call for h...

Page 45: ... Model XTP 025 or 033 See Table 41 2 Note XT steam blower installation must comply with governing codes Table 41 3 XT steam blower specifications Model Maximum capacity Shipping weight Operating weight Volume airflow Current draw at 115V 50 60 Hz Input power Noise lbs hr kg h lbs kg lbs kg cfm m3 min SDU 006E 20 9 1 14 0 6 4 11 0 5 0 106 3 0 0 16 A 17 W 49 dBA SDU 017E 50 22 7 29 0 13 2 24 0 10 9 ...

Page 46: ... Step 5 place XT humidifier below XT steam blower on wall and secure humidifier to wall 7 Push small burr of tee into loose end of condensate hose that was fed into cabinet in Step 6 8 Cut midpoint of 5 8 fill hose that connects center port on fill cup to fill connection on floor of humidifier cabinet Avoid kinks by leaving slack in fill hose for cylinder installation 9 Install tee in 5 8 fill hos...

Page 47: ...ntact After the electrical connections are made assemble the base plate onto the bottom of the steam blower with the screws provided INSTALLATION XT steam blowers Dispersion Follow the instructions below for your wall type Mount the XT steam blower using the lag bolts provided Follow the instructions below for mounting on a wood stud wall 1 Mount spanner board on wall spanning at least two studs a...

Page 48: ...The water seal is required to ensure condensate drainage from the XT steam blower and to keep steam from blowing out of the condensate hose After the water seal run the condensate hose to an open drain Cut the hose at a 45 degree angle on the end above the drain to permit a direct stream of water into the drain while maintaining an air gap The condensate hose must be installed and sized according ...

Page 49: ...which increases current flow and steam production 5 CONTROLLER INITIATES DRAIN FILL CYCLES TO FLUSH CONDUCTIVE IONS As steam production continues the concentration of conductive ions in the water increases eventually leading to increased electrical current through the water An algorithm monitors water conductivity and auto tunes drain and fill cycles to keep electrical current within demand paramete...

Page 50: ...flow if the electrodes in the steam cylinder are not submerged in water If the current rating exceeds 120 of nominal current the drain valve opens automatically As the water level drops the current rating drops back to the nominal value If the current rating exceeds 120 of the nominal current after several drainage operations the humidifier shuts down automatically OPERATION FIGURE 46 1 XT SERIES HU...

Page 51: ...ly on do not use demineralized deionized or reverse osmosis water and confirm that drain valve is closed If the force of air exiting water supply lines blows fill cup cap off during first fill cycle this is not a sign of defect or a cause for concern simply replace fill cup cap after all air has exited water line Verify that humidifier is level and plumb when filled with water Turn power on and confirm th...

Page 52: ...ITATION Model XTP humidifier capacity can be limited to a user specified maximum using the keypad display or Web interface From the Main menu select Tank Setup then select Capacity Adjustment for menu options WARNING Electric shock hazard Only qualified electrical personnel should perform start up procedure Contact with energized circuits can cause property damage severe personal injury or death as a...

Page 53: ...st follow the cool down procedure below COOL DOWN PROCEDURE 1 In Vapor logic keypad display Main menu select Tank Status and press Enter 2 Select Mode and press Enter 3 Select Drain and press Enter 4 Let steam cylinder drain for 5 to 10 minutes drain water is automatically tempered when drain water tempering is selected 5 Close field installed manual supply water shut off valve and allow cylinder ...

Page 54: ...gainst cabinet floor with fingers 11 Raise cylinder until drain outlet clears drain valve body and the side tabs on the cylinder have cleared the cylinder guides Remove cylinder from cabinet 12 Vacuum scale and debris out of drain valve port Note For more thorough cleaning see drain valve maintenance instructions on Page 51 13 Replace O ring in drain valve body new cylinder ships with new O ring M...

Page 55: ...lunger F spring E actuator D and plastic drain valve body G with clean water 8 Reassemble drain valve When threading actuator D into drain valve body G make sure it is not cross threaded Torque actuator into drain valve body to 18 in lb 2 0 N m 9 Plug Molex plug into its mating wire harness plug and slide cap A onto drain valve coil C 10 See Start up procedure on Page 48 if returning humidifier to...

Page 56: ... Reassemble drain valve assembly Fit mounting screws with washers insert them through drain cup plate and tighten them into drain cup See notes in Figure 51 2 7 Clean end of hose and reconnect it to drain valve body with hose clamp Plug Molex plug into its mating wire harness plug 8 See Start up procedure on Page 48 if returning humidifier to operation MODEL XTP TROUBLESHOOTING Follow the procedur...

Page 57: ...on Call for humidity not being received Check wiring and settings of high RH limit switch and airflow proving switch Water constantly runs down drain Malfunctioning drain valve Check valve function using Test Mode Debris in drain valve preventing it from closing Remove cylinder and clean debris from drain valve O ring in drain valve not properly seated in groove Remove cylinder and reposition O rin...

Page 58: ...for systems plumbed to low conductivity water and systems that operate for short cycles XT Series humidifier recommended fill water conductivity is 125 to 1250 μS cm Plumb humidifier to softened water To determine operating current attach clamp on ammeter to one of the electrode wires on top of cylinder Add add 1 4 to 1 2 tab sodium bicarbonate i e Alka Seltzer to water in cylinder increase water con...

Page 59: ...gnostics in the toolbar click Humidifier info see Firmware version below When issue began Example Always after remodel after a change in weather etc Issue description Example water leaking low humidity high humidity etc System changes Example Pressure new service new controller relocation change in maintenance etc Troubleshooting MAINTENANCE DriSteem Technical Support Have the following informatio...

Page 60: ...6 XT SERIES INSTALLATION OPERATION AND MAINTENANCE MANUAL Replacement parts Subpanel SDU option OM 7985 OM 7703 FIGURE 56 1 MODELS XTP 002 THROUGH 048 REPLACEMENT PARTS MAINTENANCE OM 8002 Euro subpanel ...

Page 61: ...230 240 277 400 V 530013 004 5 Display board Vapor logic controller 408495 004 6 Main board Vapor logic controller 183504 004 7 Kit electrode wiring plugs wires 1 red 1 black 1 white 194625 001 8 Kit cylinder 194601 9 Strainer cylinder 531006 10 Drain valve assembly see parts in Figure 51 1 194610 001 11 Fill valve assembly Models XTP 002 and 017 194623 001 Fill valve assembly Models XTP 025 throu...

Page 62: ...58 XT SERIES INSTALLATION OPERATION AND MAINTENANCE MANUAL Subpanel OM 7705 OM 7704 FIGURE 58 1 MODELS XTP 050 THROUGH 096 REPLACEMENT PARTS MAINTENANCE Replacement parts Euro Subpanel OM 8003 ...

Page 63: ...4 014 7 Kit electrode wiring plugs with wires 1 red 1 black 1 white 194625 001 Kit electrode wiring extended plugs with wires 1 red 1 black 1 white 194625 002 8 Kit cylinder XT 75 150 XT 025 050 380V 3P 194601 023 Kit cylinder XT 75 150 XT 025 050 400 600V 3P 194601 025 Kit cylinder XT 100 200 XT 033 096 380 400V 3P 194601 026 Kit cylinder XT 100 200 XT 033 096 480 600V 3P 194601 028 9 Strainer cy...

Page 64: ...lacement parts OM 7700 Table 60 1 SDU 006E and SDU 017E steam blowers Item Description Part No 1 Fan SDU 006E 120V 407109 002 Fan SDU 017E 230V 306377 Fan SDU 006E 230V 407109 102 Fan SDU 017E 120V 306376 FIGURE 60 1 SDU 006E AND SDU 017E STEAM BLOWERS MAINTENANCE ...

Page 65: ...itter duct 2 RH DSB 405884 009 Humidity transmitter room 2 RH 405883 008 Switch airflow AFS 112 150 electric 406190 Kit Y connector Models XTP 033 042 and 048 see Figure 24 1 1 Y connector stainless steel 1 x 2 DN40 x DN50 191070 101 2 steam hoses 1 DN40 12 305 mm long 4 hose clamps Kit Y tube connectors Models XTP067 through 096 see Figure 24 1 2 Y connector kits 191070 101 1 flanged tube connector...

Page 66: ...62 XT SERIES INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes ...

Page 67: ...63 XT SERIES INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes ...

Page 68: ...r such damages are sought based on breach of warranty breach of contract negligence strict liability in tort or any other legal theory even if DriSteem has notice of the possibility of such damages By purchasing DriSteem s products the purchaser agrees to the terms and conditions of this Limited Warranty EXTENDED WARRANTY The original user may extend the term of the DriSteem Limited Warranty for a...

Reviews: