4.
INSTALLATION
ASADOR 5G
– 10G – 15G – 20G – 30G – 40G
14
industrial use of the type CEE17 are suitable or those which satisfy
European norm EN 60309.
The thermal circuit breaker must be calibrated to the total rated current
and the magnetic circuit breaker calibrated to the rated current (In the case
of ovens this is only slightly higher than rated current), while the differential
mechanism must be calibrated to the 30 mA current (see Table 3.1).
The electrical socket must be easily accessible and must not require
further location after the installation of the equipment. The distance
between the equipment and the socket must be sufficient to avoid
stretching the power cable.
The power cable must never be trapped under the feet or wheels of
the equipment.
If the Power cable is damaged it must be substituted by
customer support or by a qualified service engineer so as to avoid
any risk.
The Manufacturer does not accept responsibility for damage caused by
failure to observe the abovementioned norms.
For the position of the electrical power connections, see Fig. 4.2.
Fig. 4.2 Positioning of electrical connection and plate