Complete 101 Series Installation Manual
99-25517-I001 July 2022 Rev. B
121 |
P a g e w w w . a n t h o n y i n t l . c o m
Programming, Settings, and Parameters
Sensor Button
Use the Sensor button to set dewpoint offsets to the unit in addition to the 24-hour gasket seat mode. There are 3 additional modes that the
button will go through when it is held (see modes below).
Figure K.2: Energy Controller (Dew Point Sensor)
Settings
Offset Status Indicator Mode
In addition to the factory setting, there is an option to add additional offset to the Temperature sensor. This mode is used to verify offset
setting (in addition to Dew Point tempe 10°F) the system is currently in. If the button is held for less than 10 seconds, the LED will
blink up to 4 times.
•
1 Blink
•
1 Blink of the LED indicates that there is no offset added to the (Dewpoint Tempe 10ºF) calculation
•
2 Blinks
•
2 Blinks of the LED indicate that there is a 3°F offset added to the (Dewpoint Tempe 10ºF)
calculation. The overall cut off Temperature is (Dew point Tempe 13ºF)
•
3 Blinks
•
3 Blinks of the LED indicate that there is a 9°F offset added to the (Dewpoint Tempe 10ºF)
calculation. The overall cut off Temperature is (Dew point Tempe 19ºF)
•
4 Blinks
•
4 Blinks of the LED indicate that there is a 18°F offset added to the (Dewpoint Tempe 10ºF)
calculation. The overall cut off Temperature is (Dew point Tempe 28ºF)
Releasing the button during this time period will return the unit to normal operation. The first mode is intended to inform the technician if
there is an offset being added to the dewpoint calculation.
Sensor button
RED LED