Operation & Maintenance Manual
Maintenance
72
22637300
OVERCURRENT RELAY ADJUSTMENT (Set Dial on the OCR Relay)
Overcurrent Relay Adjustment
KVa
Setting ±
0.1
AMPS
25
2.1
34
40
2.3
47
60
1.9
77
70
1.9
96
80
2.2
109
90
2.4
124
125
2.1
165
145
2.4
190
185
2.0
242
240
2.0
314
290
1.9
384
315
2.1
415
450
2.0
603
570
2.4