Operating Instructions
Operation & Maintenance Manual
22637300
63
Gen >V Sd
Shutdown level for generator over voltage. All three phases are checked. Maximum out of
three is used.
Gen >V Wrn
Warning level for generator over voltage. All three phases are checked. Maximum out of three
is used.
Gen <V Sd
Shutdown level for generator under voltage. All three phases are checked. Minimum out of
three is used.
Gen <V Wrn
Warning level for generator under voltage. All three phases are checked. Minimum out of three
is used.
Gen V del
Delay for generator under voltage and over voltage alarm.
Volt unbal
Threshold for generator voltage unbalance alarm.
Volt unbal del
Delay for generator voltage unbalance alarm.
Gen >f SD
Shutdown level for generator over frequency.
Gen>f Wrn
Warning level for generator over frequency.
Gen <f Wrn
Warning level for generator under frequency.
Gen <f SD
Shutdown level for generator under frequency.
Gen f del
Delay for generator under frequency and over frequency alarm.
Summary of Contents for G10WMI-2D-T2
Page 2: ...2 ...
Page 5: ...22637300 5 Drawbar Notice ...
Page 7: ...22637300 7 Safety Symbols ...
Page 11: ...Safety Symbols Operation Maintenance Manual 22637300 11 ...
Page 12: ...12 22637300 Always use genuine replacement parts ...
Page 13: ...22637300 13 Safety ...
Page 21: ...22637300 21 General Data ...
Page 28: ...28 22637300 ...
Page 29: ...22637300 29 Operating Instructions ...
Page 36: ...Operation Maintenance Manual Operating Instructions 36 22637300 20 18 19 21 22 ...
Page 54: ...Operation Maintenance Manual Operating Instructions 54 22637300 ...
Page 55: ...Operating Instructions Operation Maintenance Manual 22637300 55 ...
Page 65: ...22637300 65 Maintenance ...
Page 75: ...22637300 75 Alternator Installation and Maintenance ...
Page 103: ...Alternator Installation and Maintenance Operation Maintenance Manual 22637300 103 ...