DUAL CLIMA
12
6.2
Operation with room thermostat
The
DUAL CLIMA
heat pump incorporates a connection prepared for the installation of a room
chrono-thermostat or room thermostat (see
"Room Thermostat Installation"
), which will allow the
operation of the heat pump to be controlled depending on the temperature in the interior of the
home. Optionally,
DOMUSA TEKNIK
offers a wide range of such devices in its product catalogue.
Once the thermostat is installed in your home, select the desired temperature and operating
periods, if it is a chrono-thermostat (see the Room-Thermostat Manual). The heat pump will turn on
and activate the heating/cooling operation mode selected in it (AUTO, Heating or Cooling) until the
temperature set in the room thermostat is reached. When the desired temperature in the home is
reached, the heating and/or cooling service of the heating/cooling installation will be disabled,
shutting down the operation of the heat pump. The screen of the electronic controller will display
the icon, showing that the heat pump has been switched off by the room thermostat (Standby).
The operation with the room thermostat will not affect the DHW service, keeping it enabled
regardless of the status of the thermostat.
The installation of a room thermostat will optimise the installation
’
s performance, adapting the
heating and/or cooling to the requirements of your home and obtaining enhanced comfort.
Additionally, if the thermostat allows the operating hours to be programmed (chrono-thermostat),
it can adapt the installation to the hours of use of the installation.
6.3
Operation with a room sensor
The
DUAL CLIMA
heat pump incorporates a connection prepared for the installation of a room
temperature sensor (see
"Room Sensor Installation"
), through which the electronic controller will be
able to read the temperature in the interior of the home, allowing the management of the
installation of heating/cooling depending on the temperature of the interior of your home. The
room sensor is supplied as an optional accessory of the heat pump, except for the PACK items of
the aerothermal line, in which it will be supplied by default within the PACK.
Once the room sensor is installed in your home, select the desired room temperature, adjusting it in
parameter
P29
of the Technical menu (see
"Technical Menu"
). In addition, the Heating temperature
and Cooling temperature of the heat pump (if any) should be adjusted (see
"Temperature
Selection"
). The heat pump will turn on and activate the heating/cooling operating mode selected
in it (AUTO, Heating or Cooling) until the set temperature is reached in the heat pump. In turn, the
circulation pump of the heating/cooling installation will be activated until the desired room
temperature is reached (set in parameter
P29
of the Technical menu). When the desired room
temperature is reached in the home, the circulator pump of the heating/cooling installation will be
deactivated, delivering no heat or cold to the room.
The operation with the room sensor will not affect the DHW service (if any), keeping it enabled
regardless of the status of the thermostat.
The installation of a room sensor will optimise the installation
’
s performance, adapting the heating
and/or cooling to the requirements of your home and providing enhanced comfort features. In
addition, by means of the programming integrated into the heat pump, the service can be adapted
to the hours of use of the installation.