DUAL CLIMA
10
In addition to the temperature values, in the Heating mode, the "AU"
value can be selected as the
setpoint, by pressing
after selecting the value 10 ºC. Select this value to enable the operation
according to the outdoor weather conditions for that mode. The adjustment of the setpoint
temperature will be carried out automatically by the electronic controller according to the
temperature measured outside the home, according to operating curves pre-set by the installer or
the Official Technical Assistance Service (see
"Operation According to Outdoor Weather Conditions"
).
NOTE: If automatic operation is selected according to the external climatic conditions ("AU"),
an incorrect adjustment of the operating curves may cause the heating installation not
to generate the desired comfort in the home, failing to provide heating in extreme
weather conditions of cold and/or causing overheating in hot weather conditions.
5.3
Adjusting the DHW mode setpoint temperature
The selectable value range for the DHW mode is 10~60 ºC. The
default factory value is 50 ºC, and by means of
buttons it may
increase or decrease, respectively. Once the desired value has been
selected, press
button to save it.
If the desired temperature in the tank is higher than 50 ºC, it is essential to install an auxiliary heat
source in the tank (electric heating resistor, auxiliary boiler, etc.). The
DUAL CLIMA
heat pump will
heat the water in the tank to 50 ºC and, from this temperature, activate the auxiliary source to reach
the desired upper temperature.
5.4
Adjusting the Anti-Legionella function parameters
The operation of the anti-legionella function will depend on 4 adjustable parameters, which will be
selected by successive press of
button.
Anti-Legionella Temperature
The selectable value range for the Anti-Legionella function is
60~70 ºC. The default factory value is 65 ºC, and by means of
buttons it may increase or decrease, respectively. Once the
desired value has been selected, press
button to save it.
Frequency
This parameter adjusts the periodicity (in days) at what the anti-
legionella function will be activated. The selectable value range
is 7~99 days. The default factory value is 7 days, and by means of
buttons it may increase or decrease, respectively. Once
the desired value has been selected, press
button to save it.
Start Time
This parameter adjusts the time at what the anti-legionella
function will be activated. The selectable value range is 0~23
hours. The default factory value is 1 (at 1:00 am), and by means
of
buttons it may increase or decrease, respectively. Once
the desired value has been selected, press
button to save it.