horizontal coaxial removal and intake systems
Removal of combustion products and air intake may be made via concentric Ø60/100 pipes (60 mm
for combustion product removal and Ø100 mm for air intake) or through concentric Ø80/125 pipes
(80 mm for combustion product removal and Ø125 mm for air intake).
It is advisable to fit the pipe in a slightly upwardly-inclined direction, at around 2-3º, to prevent any
water or condensation from dripping out.
Standard removal system
Extended removal system
Ø60/100
=> Maximum total length: A = 10 m.
Ø80/125
=> Maximum total length: A = 20 m.
Ø60/100
=> Max. length: A + B -(1x45º elbow)=10 - 1.0=9 m.
Ø80/125
=> Max. length: A+B -(1x45º elbow)=20 - 1.0=19m.
60/100 => Cod. CGAS000375
80/125 => Cod. CGAS000322
60/100 => Cod. CGAS000318
80/125 => Cod. CGAS000082
60/100 => Cod. CGAS000317
80/125 => Cod. CGAS000081
1 m horizontally-arranged outlet kit
90º coaxial elbow
60/100 => Cod. CGAS000316
80/125 => Cod. CGAS000080
1m coaxial duct
45º coaxial elbow
Coaxial tuve adaptor kit
60/100 => Cod. CGAS000399
80/125 => Cod. CGAS000221
In case of installing the boiler in type C
13
in double duct, it must be taken into account
that the combustion product removal and air intake ducts must be installed within a
50cm square. In addition, the recommended minimum distance between both ducts is
40cm.