Fusion Hybrid Gas Condens
24
5.5
Type C
33
vertical coaxial removal and intake systems
Removal of combustion products and air intake may be made via concentric Ø60/100 pipes (60 mm
for combustion product removal and Ø100 mm for air intake) or through concentric Ø80/125 pipes
(80 mm for combustion product removal and Ø125 mm for air intake).
Standard removal system
Extended removal system
Ø60/100
=> Maximum total length: A = 11 m.
Ø80/125
=> Maximum total length: A = 22 m.
Ø60/100
=> Max. length: A + B - (1 x 45º elbow)= 11 - 1 =
10 m.
Ø80/125
=> Max. length: A + B - (1 x 45º elbow)= 22 - 1 =
21 m.
60/100 => Cod. CGAS000380
80/125 => Cod. CGAS000315
60/100 => Cod. CGAS000314
80/125 => Cod. CGAS000082
60/100 => Cod. CGAS000317
80/125 => Cod. CGAS000081
1 m vertical-arranged outlet kit
90º coaxial elbow
60/100 => Cod. CGAS000316
80/125 => Cod. CGAS000080
1 m coaxial duct
45º coaxial elbow
Teja negra
Cód. CGAS000074
Flar roof
Sloped roof
Teja negra
Cód. CGAS000075
Coaxial tuve adaptor kit
60/100 => Cod. CGAS000399
80/125 => Cod. CGAS000221
In case of installing the boiler in type C
33
in double duct, it must be taken into account that the
combustion product removal and air intake ducts must be installed within a 50cm square. In
addition, the recommended minimum distance between both ducts is minimum 40cm.