Subnetwork Installation Guidelines
Network Guide
87
Figure 55: Setting the Allure EC-Smart-Air or EC-Smart-Comfort communicating sensor’s Subnet ID
Address
shows an example of how to set the Allure EC-Smart-Air or EC-Smart-Comfort com-
municating sensor's Subnet ID address DIP switch to 6 and how to set the EOL termination to
ON.
Allure EC-Smart-Comfort / EC-Smart-Air
Front Cover, Interior View
S et the S ubnet
ID A ddress
E OL
Termination
RJ-45 S ubnetwork P ass-
Through Connectors
Table 20: Allure EC-Smart-Air or EC-Smart-Comfort communicating sensor's Subnet ID Address DIP Switch
Settings
Switch Position
Allure EC-Smart-Air or EC-Smart-Comfort
communicating sensor's Subnet ID Address
1
2
3
4
OFF
OFF
OFF
OFF: EOL disabled
ON: EOL enabled
1
ON
OFF
OFF
1
OFF
ON
OFF
2
ON
ON
OFF
3
OFF
OFF
ON
4
ON
OFF
ON
5
OFF
ON
ON
6
Summary of Contents for ECB-VAV