BACnet MS/TP Communication Data Bus Fundamentals
Network Guide
13
BACnet/IP to MS/TP Adapter
RT-
RT+
COM
BACnet/IP to MS/TP Router
-
+
SC
Table 1: Common Identification Labels for BACnet MS/TP Data Bus Polarity for Distech Controls' Products
Distech Controls Product
Typical Data Bus Connection Terminals
Inverting
Non-inverting
Reference
Except for an EC-BOS and ECB-PTU Line-Powered Controllers, never connect the
shield of the BACnet MS/TP data bus to the Reference terminal. See
on page 24 for more information.
Table 2: Common Identification Labels for BACnet MS/TP Data Bus Polarity for other Manufacturers
Device Manufacturer
Typical Data Bus Connection Terminal
Inverting
Non-inverting
Reference
Common identification labels
for BACnet MS/TP data bus
polarity by other Manufactur-
ers
B
A
SC
-
+
G
TxD-/RxD-
TxD+/RxD+
GND
U-
U+
COM
RT-
RT+
REF
Sig-
Sig+
Data-
Data+
When interfacing with BACnet MS/TP devices from other manufacturers, refer to
the documentation provided with the device to correctly wire the device.