56
Network Guide
For more information and detailed explanations on network topology and wire length restric-
tions refer to the Junction Box and Wiring Guideline for Twisted Pair L
ON
W
ORKS
® Networks.
These guides can be downloaded from Echelon's web site at
TP/FT 10 Cable Specifications
Two types of cable are recommended for TP/FT 10 channel installations.
Type 1:
22 AWG (Ø0.65mm), 1 twisted pair (1P), stranded conductor (STR), tinned copper (TNC),
PVC insulation, PVC jacket, unshielded, plenum FT6, CSA 600V, UL 300V.
•
As a general rule, the TP/FT 10 channel communication cables should not be
run close to high voltage power cables.
•
All wiring must comply with applicable national, state and local wiring electrical
codes, ordinances, and regulations.
Table 11: TP/FT 10 Channel Attributes
Parameter
Details
Nickname
Free Topology
Raw Bit rate
78kbps
Packets per second
144/168
Peak traffic
180/210
Topology
Free, Bus
Termination
-One per segment in free topology
-Two per segment in bus topology
Maximum number of
devices per segment
64
Note:
A maximum of 128 devices per channel can be installed
on a TP/FT 10 when a router or repeater is used. See
on page 59 for more information.
Table 12: TP/FT 10 Type 1 Cable Attributes
Parameter
Details
Conductor Gauge (AWG)
Metric Conversions for Wire Gauge
on
page 133).
Conductor Count
2 Conductors (twisted pair)
Conductor Type
Stranded conductor
Material
Tinned copper
Plenum
Plenum rated
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...