Subnetwork Installation Guidelines
Network Guide
83
Figure 53: Setting the EOL Terminations on the Cat 5e Cable Subnetwork Data Bus for the ECB/ECL-
PTU Series Controllers
EOL Terminations for the ECB/ECL-600 Series Controllers
When one or more Allure Series sensors are installed with an ECB/ECL-600, only the EOL ter-
minations of the ECB/ECL-600 and the last Allure Series sensor are set to ON. All other Allure
Series sensors must have their EOL terminations set to OFF. This is shown below:
Depending on the type of expansion module, the subnetwork data bus EOL may be
set by configuring jumpers or DIP switches. Refer to the expansion module's hard-
ware installation guide for how to identify and set a room devices' built-in EOL termi-
nations.
Light or Sunblind
Expansion Module
Controller Series:
ECL-PTU
ECB-PTU
Typical Room Devices
Cat 5e Cable Subnetwork Bus
Back of
EC-Multi-Sensor
Place jumper to enable the EOL
at the last extension module at
the end of the Bus, otherwise
remove the jumper
RJ-45 Subnet Connector
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...