BACnet MS/TP Communication Data Bus Fundamentals
Network Guide
25
Figure 8: Typical Cable-Shield Grounding Requirements for a BACnet MS/TP Data Bus Segment with a Building
Controller located in the Middle of the Data Bus
Figure 9: Typical Cable-Shield Grounding Requirements for a BACnet MS/TP Data Bus Segment without a
Building Controller
ECB-PTU Line-Powered Data Bus Controller Shield Grounding
Requirements
The shield on each data bus segment must be connected to the electrical system ground at
one point only, for example, at the Data Bus Master (Building Controller) if there is one, as
shown below in
and
. On data bus segments without a Data Bus Master,
the ideal point to ground the shield is in the middle of the data bus segment as shown in
Figure 10: Typical Cable-Shield Grounding Requirements for a BACnet MS/TP Data Bus Segment with a Building
Controller located in the End of the Data Bus
Typical BACnet 24VAC-
Powered Controller
Data Bus Shield:
Isolate with
electrical tape
Data Bus Shields: Twist
together and Isolate
with electrical tape
Typical BACnet 24VAC-
Powered Controller
Typical BACnet 24VAC-
Powered Controller
Data Bus: Shielded Twisted Pair Cable
NE
T+
NE
T
-
NE
T+
NE
T
-
NE
T+
NE
T
-
Bus Master (Building Controller)
Typical EC-BOS Device
+
-
S
Typical BACnet 24VAC-
Powered Controller
NE
T+
NE
T
-
Data Bus Shield:
Isolate with
electrical tape
Data Bus Shields:
Connect to the ‘S’
terminal
Electrical
System
Ground
The shield of the data bus must be connected to
the electrical system ground at one point only –
usually at the Building Controller , when present
Data Bus Shields: Twist
together and Isolate
with electrical tape
Typical BACnet 24VAC-
Powered Controller
Data Bus Shield:
Isolate with
electrical tape
Typical BACnet 24VAC-
Powered Controller
Data Bus Shields: Twist
together and Isolate
with electrical tape
Typical BACnet 24VAC-
Powered Controller
Data Bus Shields: Twist
together and Isolate
with electrical tape
Typical BACnet 24VAC-
Powered Controller
Data Bus: Shielded Twisted Pair Cable
NE
T+
NE
T
-
NE
T+
NE
T
-
NE
T+
NE
T
-
NE
T+
NE
T
-
Typical BACnet 24VAC-
Powered Controller
NE
T+
NE
T
-
Data Bus Shield:
Isolate with
electrical tape
Electrical
System
Ground
The shield of the data bus must be connected to
the electrical system ground at one point only,
ideally in the middle of the data bus as shown
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...