Subnetwork Installation Guidelines
Network Guide
71
Subnetwork Module Compatibility and Supported Quantity
Charts
Not all subnetwork modules work with all controller models: The subnetwork module compati-
bility for an individual controller is shown in the table below along with the maximum supported
quantity of room devices and extension modules. The Subnet ID address of all subnet devices
must be set to be within the shown addressing range.
Adding devices to the subnetwork decreases system responsiveness which may
cause delays executing commands needing a fast response such as lighting and
shades/sunblind commands.
Table 16: Subnetwork Module Compatibility and Maximum Supported Quantity Chart
Controller
Model
Subnetwork Data Bus Device
Permitted Subnet
ID Addressing
Range
1
Maximum
Quantity Allowed
ECL-VAV
ECB-VAV
Allure EC-Smart-Vue series
1 to 4
See below
2
,
4
Allure EC-Smart-Comfort series
1 to 4
Allure EC-Smart-Air sensor series
EC-Multi-Sensor series
1 to 4
ECx-Light-4 / ECx-Light-4D / ECx-
Light-4DALI
1 to 4
ECx-Blind-4 / ECx-Blind-4LV
ECx-4XX I/O Extension Modules
-
Not Supported
ECx-Display
-
Not Supported
ECL-VAVS
ECL-VAV-N
ECB-VAVS
ECB-VAV-N
Allure EC-Smart-Vue series
1 to 4
4
3
Allure EC-Smart-Comfort series
1 to 4
Allure EC-Smart-Air series
EC-Multi-Sensor series
-
Not Supported
ECx-Light-4 / ECx-Light-4D / ECx-
Light-4DALI
-
Not Supported
ECx-Blind-4 / ECx-Blind-4LV
-
Not Supported
ECx-4XX I/O Extension Modules
-
Not Supported
ECx-Display
-
Not Supported
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...