100
Network Guide
For ECB Series controllers only, during commissioning, the Allure EC-Smart-Vue sensor is
used to set the controller's BACnet® MAC Address. Set the connected ECB Series controller's
MAC Address as follows:
1.
Connect an Allure EC-Smart-Vue sensor to the controller with a Cat 5e patch cable. Wait
for the display to show the room temperature.
2.
Press and hold the Menu button
for 5 seconds to enter the password menu. 10000 is
shown on the display.
3.
Use the down button
to set the number to 9995 (this is the default password).
4.
Press the Menu button
to submit the password. Upon submitting the password, the
GEN CFG
menu appears on the display.
5.
Press the down button
once to enter the
GEN CFG
submenu. The
MAC ADDRESS
menu is shown with the current controller's BACnet MAC Address.
6.
Use the up and down buttons to set the controller's MAC Address. Only addresses from 1
to 127 are recommended to be used.
7.
Press the
Menu
button
once to apply the value.
8.
Press and hold the
Menu
button
for 5 seconds to exit the configuration menu.
Once the controller's communication network is operational, the controller can be programmed
with EC-
gfx
Program. For each Allure EC-Smart-Vue sensor, set its Subnet ID number to the
block number of its associated
CommSensor
block in EC-
gfx
Program. This is done in the
Allure EC-Smart-Vue sensor's
GEN CFG
menu under
SUBNET ID
.
OR
Screen Timeout: 15 seconds
OR
Screen Timeout: 15 seconds
OR
Screen Timeout: 30 seconds
OR
Screen Timeout: 30 seconds
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...