82
Network Guide
Figure 51: Setting the EOL Terminations on the Cat 5e Cable Subnetwork Data Bus for the ECB/ECL-
VAV Series and ECB/ECL-103 to -400 Controllers
Figure 52: Setting the EOL Terminations on the Cat 5e Cable Subnetwork Data Bus for the ECB/ECL-
VAV Series and ECB/ECL-103 to -400 Controllers (Allure EC-Smart-Comfort)
Typical Room Devices
Cat 5e Cable Subnetwork Bus
EOL set to ON
at the last
sensor at the
end of the Bus
ON
EO
L
OFF
Controller Series:
· ECL-VAVS /
ECL-VAV
· ECL-PTU
· ECL-103
· ECL-203
· ECL-300
· ECL-400
Back of Allure
EC-Smart-Vue
· ECB-VAVS /
ECB-VAV
· ECB-PTU
· ECB-103
· ECB-203
· ECB-300
· ECB-400
Remove the
EOL jumper
ECx Subnet
Adapter
Typical Room Devices
Cat 5e Cable Subnetwork Bus
EOL set to ON at
the last sensor at
the end of the Bus
Controller Series:
· ECL-VAVS /
ECL-VAV
· ECL-PTU
· ECL-103
· ECL-203
· ECL-300
· ECL-400
Back of Allure
EC-Smart-Comfort
· ECB-VAVS /
ECB-VAV
· ECB-PTU
· ECB-103
· ECB-203
· ECB-300
· ECB-400
Remove the
EOL jumper
ECx Subnet
Adapter