EN-16
6.1
English
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active when the temperature is raised.
Operations to raise the temperature that
exceed a week day are activated or deactivated
at the end of each day accordingly.
N
T1
T2
Y
Heating circuit 2
and 3
Heating
Sets the room set temperature for silent
cooling.
The actual value is measured by room climate
control station 1/2
15.0 °C
...
20.0 °C
...
30.0 °C
Cooling function
Heating circuit 2
and 3
Raises the minimum permissible flow
temperature calculated from the measured
values from room climate control station 1/2. A
raised value reduces the risk of condensate
forming.
1,5K
…3,5K…
5K
Cooling function
Heating circuit 2
and 3
Settings for cooling operation
Cooling function
Sets the time programs for dynamic cooling
Cooling function
Dyn. cooling
Sets the times during which dynamic cooling is
blocked.
00:00
...
23:59
Cooling function
Dyn. cooling
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active for a block. Blocks that exceed
a weekday are activated or deactivated at the
end of each day accordingly.
N
T1
T2
Y
Cooling function
Dyn. cooling
Setting to specify whether a second chiller is to
be used in the system.
No
Yes
Cooling function
Sets the external temperature below which
cooling with reversible brine HP or passive
cooling is interrupted.
-20 °C
...
3 °C
...
35 °C
Cooling function
Brine heat pump
If the current return set temperature for passive
cooling minus hysteresis is greater than the
current brine temperature, passive cooling
occurs.
0.1K
...
2.0K
...
9.9K
Cooling function
passiv
Brine heat pump
Setting for DHW preparation
Domestic hot water
For heat pumps with 2 compressors, this sets
the external temperature below which DHW
preparation is carried out with 2 compressors.
-30 °C
...
-25 °C
...
35 °C
(10 °C HT)
Hot water
2 compressors
In parallel operation, the maximum number of
compressors available in the network is
displayed here. The number of these that are to
be used for domestic hot water preparation can
be selected.
0
...
1
...
28
Hot water
Paralell connection
Master controller
The hysteresis of the domestic hot water set
temperature forms the neutral zone below
which a request for domestic hot water will be
issued.
2K
...
15K
Hot water
Sensor
Does hydraulic isolation of the cooling circuit
and the domestic hot water circuit allow for
parallel operation of cooling and domestic hot
water?
No
Yes
Hot water
Sensor
Passive cooling
function
Sets the desired domestic hot water
temperature
30 °C
...
60 °C
...
85 °C
Hot water
Sensor
System-specific parameters
Setting range
Display