Configuring the Heat Pump Heating System
6.1
Englis
h
Is the sensor for heating circuits 2/3 installed in
the flow or return flow? Setting the return flow
will result in the calculated set value of heating
circuit 2 also being used for heat pump heating
requests. Setting the flow means it is only used
for mixer control.
Return flow
Flow
Heating circuit 2
and 3
Heating
The heating curve end point should be set
according to the design of the heating system.
This should be done by entering the maximum
flow or return flow temperature depending on
the position of the sensor.
20 °C
...
30 °C
...
70 °C
Heating circuit 2
and 3
Regulation according
to external
temperature
Parallel shift of the set heating curve for heating
circuit 2. By pressing the arrow buttons once,
the heating curve is shifted by 1 °C upwards
(hotter) or downwards (colder).
Indicator bar
Heating circuit 2
and 3
Heating
Sets the desired return flow set temperature
when fixed setpoint regulation is selected
15 °C
...
40 °C
...
60 °C
Heating circuit 2
and 3
Fixed setpoint for
heating circuits 2
and 3
Different maximum temperatures are
permissible for panel and radiator heating
systems. The upper limit of the set temperature
can be set between 25 °C and 70 °C.
25 °C
...
50 °C
...
70 °C
Heating circuit 2
and
Heating3
The return flow set temperature hysteresis
forms the neutral zone for operation of the heat
pump.
0.5K
...
2K
Heating circuit 2
and 3
Heating
The runtime between the OPEN and CLOSED
end positions varies according to the mixer
used. The mixer runtime should be adjusted to
ensure optimum temperature regulation.
1 min
...
4 min
...
6 min
Heating circuit 2
and 3
Heating
Settings to lower the heating characteristic
curve of heating circuit 2/3
Heating circuit 2
and 3
Heating
Sets the time during which the temperature in
heating circuit 2/3 is to be lowered.
00:00
...
23:59
Heating circuit 2
and 3
Heating
Sets the temperature value by which the
heating characteristic curve of heating circuit 2/
3 is to be lowered when the temperature is
lowered.
0K
...
19K
Heating circuit 2
and 3
Heating
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active when the temperature is
lowered. Operations to lower the temperature
that exceed a weekday are activated or
deactivated at the end of each day accordingly.
N
T1
T2
Y
Heating circuit 2
and 3
Heating
All settings to raise the heating characteristic
curve of heating circuit 2/3
Heating circuit 2
and 3
Heating
Sets the time during which the temperature in
heating circuit 2/3 is to be raised.
00:00
...
23:59
Heating circuit 2
and 3
Heating
Sets the temperature value by which the
heating characteristic curve of heating circuit 2/
3 is to be raised when the temperature is
raised.
0K
...
19K
Heating circuit 2
and 3
Heating
System-specific parameters
Setting range
Display