Page 24
23
Dialog® Lighting Control System
Constant Lighting Controller
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus. You access
the configuration for each of these submenus by selecting the corresponding
button:
1.
C.L.C. Functions > Basic
2.
C.L.C. Functions > Groups
3.
C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant Lighting
Controller (CLC) local sensor. The sensor has three types of settings:
Threshold Trigger
- triggers a relay output to
ON
when the measured light
level goes below the
Low Level Set Point
and triggers the output to
OFF
when the light level goes above the
High Level Set Point
value
.
Open Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the controlling
sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are
sensors when a new Output Mode is created.
1.
To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the
end of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on
the screen to adjust the configuration.
C
M
Y
CM
MY
CY
CMY
K
23
Dialog® Lighting Control System
Constant Lighting Controller
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus. You access
the configuration for each of these submenus by selecting the corresponding
button:
1.
C.L.C. Functions > Basic
2.
C.L.C. Functions > Groups
3.
C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant Lighting
Controller (CLC) local sensor. The sensor has three types of settings:
Threshold Trigger
- triggers a relay output to
ON
when the measured light
level goes below the
Low Level Set Point
and triggers the output to
OFF
when the light level goes above the
High Level Set Point
value
.
Open Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the controlling
sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are
sensors when a new Output Mode is created.
1.
To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the
end of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on
the screen to adjust the configuration.
C
M
Y
CM
MY
CY
CMY
K
23
Dialog® Lighting Control System
Constant Lighting Controller
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus. You access
the configuration for each of these submenus by selecting the corresponding
button:
1.
C.L.C. Functions > Basic
2.
C.L.C. Functions > Groups
3.
C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant Lighting
Controller (CLC) local sensor. The sensor has three types of settings:
Threshold Trigger
- triggers a relay output to
ON
when the measured light
level goes below the
Low Level Set Point
and triggers the output to
OFF
when the light level goes above the
High Level Set Point
value
.
Open Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the controlling
sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are
sensors when a new Output Mode is created.
1.
To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the
end of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on
the screen to adjust the configuration.
C
M
Y
CM
MY
CY
CMY
K
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus.
You access the configuration for each of these submenus by
selecting the corresponding button:
1. C.L.C. Functions > Basic
2. C.L.C. Functions > Groups
3. C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant
Lighting Controller (CLC) local sensor. The sensor has three types
of settings:
Threshold Trigger
- triggers a relay output to
ON
when the
measured light level goes below the
Low Level Set Point
and
triggers the output to
OFF
when the light level goes above the
High Level Set Point
value.
Open Loop
- constantly adjusts the dimming levels of each output
in response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each
output in response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the
controlling sensor. Output type is also displayed with r = relay and d
= dimmer. Outputs are sensors when a new Output Mode is created.
1. To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the end
of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on the
screen to adjust the configuration.
Constant Lighting Controller
Constant Lighting Control Functions Menu
To create a new Output Mode:
1)
2)
3)
b)
a)
23
Dialog® Lighting Control System
Constant Lighting Controller
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus. You access
the configuration for each of these submenus by selecting the corresponding
button:
1.
C.L.C. Functions > Basic
2.
C.L.C. Functions > Groups
3.
C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant Lighting
Controller (CLC) local sensor. The sensor has three types of settings:
Threshold Trigger
- triggers a relay output to
ON
when the measured light
level goes below the
Low Level Set Point
and triggers the output to
OFF
when the light level goes above the
High Level Set Point
value
.
Open Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the controlling
sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are
sensors when a new Output Mode is created.
1.
To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the
end of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on
the screen to adjust the configuration.
C
M
Y
CM
MY
CY
CMY
K
23
Dialog® Lighting Control System
Constant Lighting Controller
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus. You access
the configuration for each of these submenus by selecting the corresponding
button:
1.
C.L.C. Functions > Basic
2.
C.L.C. Functions > Groups
3.
C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant Lighting
Controller (CLC) local sensor. The sensor has three types of settings:
Threshold Trigger
- triggers a relay output to
ON
when the measured light
level goes below the
Low Level Set Point
and triggers the output to
OFF
when the light level goes above the
High Level Set Point
value
.
Open Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the controlling
sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are
sensors when a new Output Mode is created.
1.
To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the
end of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on
the screen to adjust the configuration.
C
M
Y
CM
MY
CY
CMY
K
23
Dialog® Lighting Control System
Constant Lighting Controller
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus. You access
the configuration for each of these submenus by selecting the corresponding
button:
1.
C.L.C. Functions > Basic
2.
C.L.C. Functions > Groups
3.
C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant Lighting
Controller (CLC) local sensor. The sensor has three types of settings:
Threshold Trigger
- triggers a relay output to
ON
when the measured light
level goes below the
Low Level Set Point
and triggers the output to
OFF
when the light level goes above the
High Level Set Point
value
.
Open Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the controlling
sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are
sensors when a new Output Mode is created.
1.
To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the
end of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on
the screen to adjust the configuration.
C
M
Y
CM
MY
CY
CMY
K
23
Dialog® Lighting Control System
Constant Lighting Controller
Constant Lighting Controller Menus
Constant Lighting Control Functions Menu
The Constant Lighting Control Functions menu has three submenus. You access
the configuration for each of these submenus by selecting the corresponding
button:
1.
C.L.C. Functions > Basic
2.
C.L.C. Functions > Groups
3.
C.L.C. Functions > Presets
1. Outputs
The
Outputs
screen displays all outputs controlled by a Constant Lighting
Controller (CLC) local sensor. The sensor has three types of settings:
Threshold Trigger
- triggers a relay output to
ON
when the measured light
level goes below the
Low Level Set Point
and triggers the output to
OFF
when the light level goes above the
High Level Set Point
value
.
Open Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level coming into the room.
Closed Loop
- constantly adjusts the dimming levels of each output in
response to the measured light level inside the room.
The outputs are listed by type of CLC setting in the order of the controlling
sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are
sensors when a new Output Mode is created.
1.
To create a new Output Mode:
a)
Select the
Add Mode
link. You may have to scroll to the
end of the list.
b)
Select the
CLC setting
and select the
OK
button.
c)
Select the
target type
and select the
OK
button.
d)
Select the
controlling output
and select the
OK
button.
e)
The new output mode is displayed. Use the buttons on
the screen to adjust the configuration.
C
M
Y
CM
MY
CY
CMY
K
d)
e)
c)