Dialog® Lighting Control System

Constant Lighting Controller

Constant Lighting Controller Menus
Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. You access 

the configuration for each of these submenus by selecting the corresponding 

button:

1. 

C.L.C. Functions > Basic

2. 

C.L.C. Functions > Groups

3. 

C.L.C. Functions > Presets 

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant Lighting 

Controller (CLC) local sensor. The sensor has three types of settings:

Threshold Trigger

 

- triggers a relay output to 

ON

 when the measured light 

level goes below the 

Low Level Set Point

 and triggers the output to 

OFF

 

when the light level goes above the 

High Level Set Point 

value

.

Open Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level coming into the room. 

Closed Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level inside the room. 

The outputs are listed by type of CLC setting in the order of the controlling 

sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are 

sensors when a new Output Mode is created. 

1. 

To create a new Output Mode:

a) 

Select the 

Add Mode

 link. You may have to scroll to the 

end of the list.

b) 

Select the 

CLC setting

 and select the 

OK

 button.

c)

 Select the 

target type

 and select the 

OK

 button.

 

d) 

Select the 

controlling output

 and select the 

OK

 

button. 

 

e) 

The new output mode is displayed. Use the buttons on 

the screen to adjust the configuration.

 

C

M

Y

CM

MY

CY

CMY

K

23

Dialog® Lighting Control System

Constant Lighting Controller

Constant Lighting Controller Menus
Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. You access 

the configuration for each of these submenus by selecting the corresponding 

button:

1. 

C.L.C. Functions > Basic

2. 

C.L.C. Functions > Groups

3. 

C.L.C. Functions > Presets 

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant Lighting 

Controller (CLC) local sensor. The sensor has three types of settings:

Threshold Trigger

 

- triggers a relay output to 

ON

 when the measured light 

level goes below the 

Low Level Set Point

 and triggers the output to 

OFF

 

when the light level goes above the 

High Level Set Point 

value

.

Open Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level coming into the room. 

Closed Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level inside the room. 

The outputs are listed by type of CLC setting in the order of the controlling 

sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are 

sensors when a new Output Mode is created. 

1. 

To create a new Output Mode:

a) 

Select the 

Add Mode

 link. You may have to scroll to the 

end of the list.

b) 

Select the 

CLC setting

 and select the 

OK

 button.

c)

 Select the 

target type

 and select the 

OK

 button.

 

d) 

Select the 

controlling output

 and select the 

OK

 

button. 

 

e) 

The new output mode is displayed. Use the buttons on 

the screen to adjust the configuration.

 

C

M

Y

CM

MY

CY

CMY

K

23

Dialog® Lighting Control System

Constant Lighting Controller

Constant Lighting Controller Menus
Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. You access 

the configuration for each of these submenus by selecting the corresponding 

button:

1. 

C.L.C. Functions > Basic

2. 

C.L.C. Functions > Groups

3. 

C.L.C. Functions > Presets 

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant Lighting 

Controller (CLC) local sensor. The sensor has three types of settings:

Threshold Trigger

 

- triggers a relay output to 

ON

 when the measured light 

level goes below the 

Low Level Set Point

 and triggers the output to 

OFF

 

when the light level goes above the 

High Level Set Point 

value

.

Open Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level coming into the room. 

Closed Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level inside the room. 

The outputs are listed by type of CLC setting in the order of the controlling 

sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are 

sensors when a new Output Mode is created. 

1. 

To create a new Output Mode:

a) 

Select the 

Add Mode

 link. You may have to scroll to the 

end of the list.

b) 

Select the 

CLC setting

 and select the 

OK

 button.

c)

 Select the 

target type

 and select the 

OK

 button.

 

d) 

Select the 

controlling output

 and select the 

OK

 

button. 

 

e) 

The new output mode is displayed. Use the buttons on 

the screen to adjust the configuration.

 

C

M

Y

CM

MY

CY

CMY

K

Constant Lighting Controller Menus

Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. 

You  access  the  configuration  for  each  of  these  submenus  by 

selecting the corresponding button:

1.  C.L.C. Functions > Basic

2.  C.L.C. Functions > Groups

3.  C.L.C. Functions > Presets

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant 

Lighting Controller (CLC) local sensor. The sensor has three types 

of settings:

Threshold Trigger

 - triggers a relay output to 

ON

 when the 

measured light level goes below the 

Low Level Set Point

 and 

triggers the output to 

OFF

 when the light level goes above the 

High Level Set Point

 value.

Open Loop

 - constantly adjusts the dimming levels of each output 

in response to the measured light level coming into the room. 

Closed Loop

 - constantly adjusts the dimming levels of each 

output in response to the measured light level inside the room.

The outputs are listed by type of CLC setting in the order of the 

controlling sensor. Output type is also displayed with r = relay and d 

= dimmer. Outputs are sensors when a new Output Mode is created.

1. To create a new Output Mode:

a)

  Select the 

Add Mode

 link. You may have to scroll to the end 

of the list.

b)

  Select the 

CLC setting

 and select the 

OK

 button.

c)

  Select the 

target type

 and select the 

OK

 button.

d)

  Select the 

controlling output

 and select the 

OK

 button.

e)

  The new output mode is displayed. Use the buttons on the 

screen to adjust the configuration.

Constant Lighting Controller

Constant Lighting Control Functions Menu

To create a new Output Mode:

1)

2)

3)

b)

a)

23

Dialog® Lighting Control System

Constant Lighting Controller

Constant Lighting Controller Menus
Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. You access 

the configuration for each of these submenus by selecting the corresponding 

button:

1. 

C.L.C. Functions > Basic

2. 

C.L.C. Functions > Groups

3. 

C.L.C. Functions > Presets 

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant Lighting 

Controller (CLC) local sensor. The sensor has three types of settings:

Threshold Trigger

 

- triggers a relay output to 

ON

 when the measured light 

level goes below the 

Low Level Set Point

 and triggers the output to 

OFF

 

when the light level goes above the 

High Level Set Point 

value

.

Open Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level coming into the room. 

Closed Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level inside the room. 

The outputs are listed by type of CLC setting in the order of the controlling 

sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are 

sensors when a new Output Mode is created. 

1. 

To create a new Output Mode:

a) 

Select the 

Add Mode

 link. You may have to scroll to the 

end of the list.

b) 

Select the 

CLC setting

 and select the 

OK

 button.

c)

 Select the 

target type

 and select the 

OK

 button.

 

d) 

Select the 

controlling output

 and select the 

OK

 

button. 

 

e) 

The new output mode is displayed. Use the buttons on 

the screen to adjust the configuration.

 

C

M

Y

CM

MY

CY

CMY

K

23

Dialog® Lighting Control System

Constant Lighting Controller

Constant Lighting Controller Menus
Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. You access 

the configuration for each of these submenus by selecting the corresponding 

button:

1. 

C.L.C. Functions > Basic

2. 

C.L.C. Functions > Groups

3. 

C.L.C. Functions > Presets 

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant Lighting 

Controller (CLC) local sensor. The sensor has three types of settings:

Threshold Trigger

 

- triggers a relay output to 

ON

 when the measured light 

level goes below the 

Low Level Set Point

 and triggers the output to 

OFF

 

when the light level goes above the 

High Level Set Point 

value

.

Open Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level coming into the room. 

Closed Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level inside the room. 

The outputs are listed by type of CLC setting in the order of the controlling 

sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are 

sensors when a new Output Mode is created. 

1. 

To create a new Output Mode:

a) 

Select the 

Add Mode

 link. You may have to scroll to the 

end of the list.

b) 

Select the 

CLC setting

 and select the 

OK

 button.

c)

 Select the 

target type

 and select the 

OK

 button.

 

d) 

Select the 

controlling output

 and select the 

OK

 

button. 

 

e) 

The new output mode is displayed. Use the buttons on 

the screen to adjust the configuration.

 

C

M

Y

CM

MY

CY

CMY

K

23

Dialog® Lighting Control System

Constant Lighting Controller

Constant Lighting Controller Menus
Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. You access 

the configuration for each of these submenus by selecting the corresponding 

button:

1. 

C.L.C. Functions > Basic

2. 

C.L.C. Functions > Groups

3. 

C.L.C. Functions > Presets 

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant Lighting 

Controller (CLC) local sensor. The sensor has three types of settings:

Threshold Trigger

 

- triggers a relay output to 

ON

 when the measured light 

level goes below the 

Low Level Set Point

 and triggers the output to 

OFF

 

when the light level goes above the 

High Level Set Point 

value

.

Open Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level coming into the room. 

Closed Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level inside the room. 

The outputs are listed by type of CLC setting in the order of the controlling 

sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are 

sensors when a new Output Mode is created. 

1. 

To create a new Output Mode:

a) 

Select the 

Add Mode

 link. You may have to scroll to the 

end of the list.

b) 

Select the 

CLC setting

 and select the 

OK

 button.

c)

 Select the 

target type

 and select the 

OK

 button.

 

d) 

Select the 

controlling output

 and select the 

OK

 

button. 

 

e) 

The new output mode is displayed. Use the buttons on 

the screen to adjust the configuration.

 

C

M

Y

CM

MY

CY

CMY

K

23

Dialog® Lighting Control System

Constant Lighting Controller

Constant Lighting Controller Menus
Constant Lighting Control Functions Menu

The Constant Lighting Control Functions menu has three submenus. You access 

the configuration for each of these submenus by selecting the corresponding 

button:

1. 

C.L.C. Functions > Basic

2. 

C.L.C. Functions > Groups

3. 

C.L.C. Functions > Presets 

1. Outputs

The 

Outputs

 screen displays all outputs controlled by a Constant Lighting 

Controller (CLC) local sensor. The sensor has three types of settings:

Threshold Trigger

 

- triggers a relay output to 

ON

 when the measured light 

level goes below the 

Low Level Set Point

 and triggers the output to 

OFF

 

when the light level goes above the 

High Level Set Point 

value

.

Open Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level coming into the room. 

Closed Loop 

- constantly adjusts the dimming levels of each output in 

response to the measured light level inside the room. 

The outputs are listed by type of CLC setting in the order of the controlling 

sensor. Output type is also displayed with r = relay and d = dimmer. Outputs are 

sensors when a new Output Mode is created. 

1. 

To create a new Output Mode:

a) 

Select the 

Add Mode

 link. You may have to scroll to the 

end of the list.

b) 

Select the 

CLC setting

 and select the 

OK

 button.

c)

 Select the 

target type

 and select the 

OK

 button.

 

d) 

Select the 

controlling output

 and select the 

OK

 

button. 

 

e) 

The new output mode is displayed. Use the buttons on 

the screen to adjust the configuration.

 

C

M

Y

CM

MY

CY

CMY

K

d)

e)

c)

Summary of Contents for WLC-4150-C

Page 1: ...Field Guide Centralized Lighting Control System For WLC 4150 C WLC 4150 L...

Page 2: ...WLC 4150 C Lighting Control Unit 3 Touchscreen Navigation 4 Menus Outputs 5 Groups 7 Presets 10 Modes 14 Behaviours 20 Constant Lighting Controller 22 Schedules 36 Setings 39 Event Logs 44 Notes 45 Co...

Page 3: ...Page 3 WLC 4150 C L Lighting Control Unit USB Port Power 24VAC Ethernet 2 LCD Touchscreen Display Dialog Network Power Data Power 24VAC WLC 4150 C L...

Page 4: ...ntinue The default password is dlc Enter the password and select on the OK button You can change the default password to a unique password for your facility using the Settings options 4 On the Main sc...

Page 5: ...b Select the communication bus you are configuring The default communication bus is Dialog c Select the output type Relay or Dimmer If the selected output type is a dimmer you can adjust the brightnes...

Page 6: ...bmenu group Row lists the row where it is located Col list s the column where it is located is screen allows you to list new panels installed after initialization of the stem edit panel labels and ass...

Page 7: ...y outputs to panels Dialog Lighting Control System Output Menu 1 To add a new panel a Scroll through the panel list to the unlabeled relays and select the relay Select Add Panel b Enter the new panel...

Page 8: ...enu group Total number of outputs in the group Rel number of relays in the group D number of dimmers in the group Groups Menu 7 Dialog Lighting Control System The Groups screen has four tabs 1 Label T...

Page 9: ...manufacturer and type of the contact input ufacturer is Douglas and the default value gle Also set the delay OFF time by using The default value is 30 seconds the manufacturer of the occupancy sensor...

Page 10: ...select OK header name der name select the rename link w header and select OK eader association for the header delete link re prompted to confirm the deletion eaders en displays all headers used for t...

Page 11: ...the associated outputs If you selected Mode Trigger select the associated modes Presets Menu Dialog Lighting Control System The Local Presets screen has four tabs 1 Label To modify a preset name a Sel...

Page 12: ...r and selecting Set The default value is 30 seconds Occupancy Sensor select the manufacturer of the occupancy sensor input The default value is Douglas Also set the sensitivity of the occupancy sensor...

Page 13: ...for deactivated presets A black rectangle indicates the preset has not been assigned 3 LOGs You can view the historical activity for a selected preset by selecting the LOGs tab 4 Setup a Select a pre...

Page 14: ...b continued If a selected preset is a relay you specify if it is turned on or turned off when the preset is activated If a selected output is a dimmer adjust the dimmer levels to percentage of brightn...

Page 15: ...t Modes Astro utput Modes Timeout utput Modes Flick utput Modes Perm Block des Menu 14 Dialog Lighting Control System 1 Astro The Astro screen displays all Astro Modes An Astro Mode triggers outputs d...

Page 16: ...e and select OK to modify this value 3 LOGs You can view the historical activity for a selected mode by selecting the LOGs tab Modes and select the OK button ecting the Select button elect the OK butt...

Page 17: ...rical activity for a selected mode by selecting the LOGs tab Modes nd select the OK button cting the Select button el elect the OK button y a mode electing the ACTIVATE or DEACTIVATE or activated mode...

Page 18: ...ontrol You can activate deactivate or modify a mode by a Activate or deactivate a mode by selecting the ACTIVATE or DEACTIVATE button An orange rectangle is displayed for activated modes and a blue re...

Page 19: ...e occupancy sensors associated with a specific group for a set me This mode is used to prevent outputs from switching off when ed or no activity in a room but continues to be occupied new Quiet Mode...

Page 20: ...utton e or modify a mode e a mode by selecting the ACTIVATE or DEACTIVATE is displayed for activated modes and a blue rectangle es cal activity for a selected mode by selecting the LOGs Control Functi...

Page 21: ...activate or deactivate in a or is activated When a behavior is deactivated n of outputs groups presets modes and ate in a specified order r link The new behavior appears on the list bs e t its label m...

Page 22: ...roup preset mode or schedule and select the OK button Next select the target and specify if it is on or off ehaviors etup Select the behavior from the list and select the ON ACTIONS button Select the...

Page 23: ...global sensors which are photosensor y other LCUs in the network Global sensors which are ng Controller Menus s Menu wo menus Daylight Sensors and Constant Lighting ach of these menus has multiple su...

Page 24: ...nd select the OK button d Select the controlling output and select the OK button e The new output mode is displayed Use the buttons on the screen to adjust the configuration Constant Lighting Controll...

Page 25: ...ring Preset display any of the CLC triggering presets associated with the output 2 Daylight Sensor select the associated link to modify the controlling sensor Next select the new sensor 3 CLC Function...

Page 26: ...ntrolling nsor ociated link to modify the CLC type Next sed Loop option and select the OK button he associated link to modify the value ning process First select the Interior or to set the new value a...

Page 27: ...the new value and select the OK button 3 LOGs You can view the historical activity for a selected mode by selecting the LOGs tab 2 Control continued Closed Loop a Activate or deactivate an output by...

Page 28: ...of CLC setting in the order of the controlling put type is also displayed with r relay and d dimmer Groups d to sensors when a new Group Mode is created te a new Group Mode the Add Mode link You may h...

Page 29: ...lling sensor Next select the new sensor 3 CLC Function select the associated link to modify the CLC type Next select the Open Loop or Closed Loop option and select the OK 4 High Level Target select th...

Page 30: ...t the OK button 8 Max Electric Light select the associated link to modify the value which is the brightness stable light level value in the area controlled by the CLC Use the slider to set the new val...

Page 31: ...rcentage when the ambient brightness changes Use the slider to set the new value and select the OK button nstant Lighting Controller ghting Control System trol continued ed Loop ctivate or deactivate...

Page 32: ...nsor has three types of settings rigger triggers a preset of only relays to ON when the t level goes below the Low Level Set Point and triggers the F when the light level goes above the High Level Set...

Page 33: ...tton te or configure a selected preset The procedures LC setting type as follows a preset by selecting the ACTIVATE or n displayed for activated preset and a blue ated preset EL or HIGH LEVEL button t...

Page 34: ...to adjust the dimmer out dimming level Set centage Use the slider to adjust the level and the case when the there are multiple dimmer e same sensor this value is the dimmer RATIO ON button to initiate...

Page 35: ...the commissioning process Use the slider to set the nd select the OK button me select the associated link to modify the value which is m time required for the dimmer to go from a lower to a higher rce...

Page 36: ...Page 36 3 LOGs You can view the historical activity for a selected preset by selecting the LOGs tab Constant Lighting Controller...

Page 37: ...ule by selecting the DISABLE or E button w the historical activity for a selected mode by selecting the s menu has two menus Time Schedules and Setup The as two submenus Y selecting the corresponding...

Page 38: ...button ys screen lists screen lists the schedules in order of their grouping Grouping is he same area or function with the default being Global served U When a new schedule is created it is assigned...

Page 39: ...dd Grouping link c Enter the grouping name and select the OK button 1 To change a schedule s grouping a Select the Change Grouping link b Select the new grouping by selecting the Select button Schedul...

Page 40: ...ices You can specify to discover f devices or perform a full system discovery has ten submenus You access the configuration for each of lecting the corresponding button t DIALOG al Web Server OG Disco...

Page 41: ...tware It does not apply to the creen version of the software tings stem Diagnostics screen provides information on memory mption and storage consumption ent Log Functions screen allows you to configur...

Page 42: ...screen displays the most recent 100 system events and actions in chronological order You can refresh the list by clicking the Refresh List icon Event Logs recent 100 system events and esh the list by...

Page 43: ...LIT DWLC 4150M071818 toll free 877 873 2797 direct 604 873 2797 lighting douglaslightingcontrols com www douglaslightingcontrols com Your Douglas Lighting Controls representative...

Reviews: