Page 12
4. Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you are
changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with the
activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and output
modes, as well as control other lighting control functions.
Fade Type
- sets the dimming method for the dimmers activated
by the preset. This can be controlled by a specified time in
number of seconds or by a rate of dimming change per second
to go to the next dimming-level value. To set this value, select
the Time or Rate option, select the OK button, and specify the
number of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs and
outputs associated with the preset. The default value is Douglas.
Contact Input
- select the
manufacturer
and
type
of the contact
input, which will trigger the preset. The default value for the
manufacturer is Douglas and the default value for the type is
Momentary Toggle. Also, set the
delay OFF time
by using the
slider and selecting Set. The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the occupancy
sensor input. The default value is Douglas. Also, set the sensitivity
of the occupancy sensor input and delay OFF time by selecting
Douglas
as the OCC Manufacturer and using the slider and
selecting
Set
. The default values are 10 seconds 30 seconds,
respectively.
Presets
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.
C
M
Y
CM
MY
CY
CMY
K
4. Setup (continued)
c)
c)
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.
C
M
Y
CM
MY
CY
CMY
K
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.
C
M
Y
CM
MY
CY
CMY
K
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.
C
M
Y
CM
MY
CY
CMY
K
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.
C
M
Y
CM
MY
CY
CMY
K
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.
C
M
Y
CM
MY
CY
CMY
K
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.
C
M
Y
CM
MY
CY
CMY
K
11
Dialog® Lighting Control System
Presets
4.
Setup (continued)
b)
(continued) If a selected preset is a relay, you specify if it
is turned on or turned off when the preset is activated. If
a selected output is a dimmer, adjust the dimmer levels to
percentage of brightness by using the slider.
c)
To set the parameters for the preset of the controlling
group, select the Settings button. Select the setting you
are changing and enter the new values.
The settings include the following:
Group Associated
- displays the groups associated with
the activated preset.
Mode Trigger
- operates the preset as a trigger for pre-
programmed mode. You can select specific input and
output modes, as well as control other lighting control
functions.
Fade Type
- sets the dimming method for the dimmers
activated by the preset. This can be controlled by a
specified time in number of seconds or by a rate of
dimming change per second to go to the next dimming-
level value. To set this value, select the
Time
or
Rate
option, select the
OK
button, and specify the number
of seconds (time) or percentage of brightness (rate) by
using the slider.
Switch
- select the
manufacturer
of the switch inputs
and outputs associated with the preset. The default value
is Douglas.
Contact Input
- select the
manufacturer
and
type
of the
contact input, which will trigger the preset. The default
value for the manufacturer is Douglas and the default
value for the type is Momentary Toggle. Also, set the
delay OFF time
by using the slider and selecting
Set
.
The default value is 30 seconds.
Occupancy Sensor
- select the
manufacturer
of the
occupancy sensor input. The default value is Douglas.
Also, set the sensitivity of the occupancy sensor input
and delay OFF time by selecting
Douglas
as the OCC
Manufacturer and using the slider and selecting
Set
. The
default values are 10 seconds 30 seconds, respectively.