![Detectortesters Testifire 1000 User Manual Download Page 37](http://html.mh-extra.com/html/detectortesters/testifire-1000/testifire-1000_user-manual_2487843037.webp)
8. Technical Specifications
Battery Baton: nominal 7.2V 2.2Ah NiMH rechargeable battery pack with internal overcurrent
protection connects directly to Testifire with no leads or wires.
Must be charged by Solo 726 Battery Charger (using 100-230VAC or 12VDC input).
Power source
Dependent on mode of use:
Smoke testing: <0.5A rms
Heat testing: 4-6A rms
CO testing: 2-5A rms
RFID/Bluetooth®: <150mA rms
N.B. Power consumption refers only to the duration of the actual test and may vary considerably
due to internal control algorithms.
Power consumption
Smoke
: a simulated smoke generated internally using a miniature heat exchanger and a harmless
liquid from the smoke capsule.
Normal Heat
: to test rate-of-rise and fixed temperature heat detectors up to 90ºC (194ºF).
Hi Heat:
to test rate-of-rise and fixed temperature heat detectors up to 100ºC (212ºF).
Carbon Monoxide (CO)
: CO is generated internally and blown into the detector at a
concentration of approximately 100ppm (not calibrated).
CARBON MONOXIDE (CO) IS A HARMFUL, ODOURLESS GAS AND CARE SHOULD BE
TAKEN NOT TO INHALE DIRECTLY FROM THE DUCT DURING A CO TEST.
Clearing
: clean air is blown to remove previously applied Smoke or CO.
Simultaneous Testing
: Smoke, Heat and CO (if appropriate) in any combination as
programmed by the user are all carried out in one test.
Sequential Testing
: Tests are performed according to the order that they have been
programmed by the user.
RFID Auto Mode
: Automatic testing using an RFID module fitted to Testifire and an
appropriately programmed RFID label attached to the detector.
Test modes
Battery over-current cut-out.
Default 2 minutes maximum test duration timeout.
Auto power off after 10 minutes of non-use.
CO generated on demand (no gas stored).
Safety Features
Colour coded LED user feedback.
Automatic infrared sensing of the detector.
Adjustable multi-position head.
Optional fully-automatic configuration (RFID Auto mode).
Operating Features
Optical / photoelectric and ionisation smoke detectors.
Thermal sensors (fixed temperature or rate-of-rise).
Carbon Monoxide (CO) fire sensors.
Multi-sensors or multi-criteria detectors.
Conventional, addressable or analogue addressable detectors of any of the above types.
Suitable Detector
Types
page 34
Battery Charge Time
Approx. 90 mins. (if completely discharged).
M U L T I - S T I M U L U S D E T E C T O R T E S T E R
testifire
®
Operating temperature range: +5ºC to +45ºC (41ºF to 113ºF).
Operating humidity range: 0 to 85% RH non-condensing.
Storage temperature range: -10ºC to +50ºC (14ºF to 122ºF).
Storage humidity range: 0 to 90% RH non-condensing (up to +35ºC / 95ºF).
Environment
Rated according to IEC60529 to IP20.
IP Rating