page 9
Fig. 7
Spring Clips
Spring Clip
Protector
CAUTION
DO NOT TOUCH
the black carbon tape of the CO capsule or surrounding area. The tip
and surrounding area may be hot after use.
CAUTION
insert fingers or other objects into the aperture from where the CO capsule has
DO NOT
been removed. There are very hot surfaces which may burn or become damaged if touched.
CAUTION
This symbol on the product indicates that this part of the device is susceptible to static
damage.
the contacts on the PCB on the capsule. Static electricity may damage
DO NOT TOUCH
them and contamination of the contacts must be avoided.
A
B
Fig. 8
C
B
M U L T I - S T I M U L U S D E T E C T O R T E S T E R
testifire
®
B
B
www.
testifire
.com
Back to Contents Page
4.3
Removal and Replacement of the Smoke and Carbon Monoxide (CO) Capsules
Smoke and CO capsules are non-refillable. Only replace with genuine Testifire TS3 (Smoke) and TC3 (CO)
Capsules.
Note:
Manufacturer’s warranty is conditional on the use of only genuine Testifire
replacement parts which must
be replaced in accordance with the instructions supplied.
Please observe the local regulations regarding the disposal of packaging
materials, exhausted batteries and old electronic equipment.
Empty capsules may be returned to the manufacturer for environmentally-
friendly disposal via the reseller to comply with WEEE (Waste Electrical &
Electronic Equipment) Regulations 2006.
Only use gentle pressure when inserting the capsules.
Smoke Capsule Removal Instructions
(Testifire 1000 and 2000 series)
Release the upper access cover
(Fig. 7) on the body of the Testifire
A
unit by opening it from the right hand side.
Note:
Testifire 1000
series units only have one access cover.
Squeeze the two clips (Fig. 7) on each side of the used capsule and
B
gently pull the capsule out.
Smoke Capsule Replacement Instructions
Remove the capsule from its outer carton and anti-static bag.
Remove the spring clip protector cap
(Fig. 8) from the new capsule.
C
Holding the capsule by the spring clips
(Fig. 8) with the label on the
B
underside, carefully insert the new capsule into the capsule port. Push it
into position, ensuring that the clips spring out positively on both sides
of the capsule to engage correctly with the port.
Close the Smoke access cover
(Fig. 7) securely.
A