7.10. Analog Inputs
Analog Inputs settings page is shown in Fig. 7.19. Input 1 to Input 4 are used to
measure voltage in range 0-10VDC. Input 5 to Input 8 are used to measure
temperature from 10K NTC sensors B57500M (with range temperature range -
55°C/-
67°F to +155°C/311°F).
Figure 7.19.
Analog Inputs settings
Description
- identification string of the input (max. 7 chars);
This description will appear in XML/JSON files, as well as in the Monitoring
& Control page.
Min
- the measured value used for scaling corresponding to Analog Input
value = 0:
o
For Input 1 to Input 4 range is from -9999.9 to +9999.9;
o
For Input 5 to Input 8 range is from -70.0 to +300.0 degF or -55.0 to +150.0
degC;
Max
- the measured value used for scaling corresponding to Analog Input
value = 1023:
o
For Input 1 to Input 4 range is from -9999.9 to +9999.9;
o
For Input 5 to Input 8 range is from -70.0 to +300.0 degF or -55.0 to +150.0
degC;
Label
- the label for the measured value, for example: mA, Kg, Volt ...(max. 4
chars), available for editing only for Input 1 to Input 4. For inputs 5 to 8, it is
fixed (degC or degF);
Low Threshold
- the low threshold for the measured value:
o
For Input 1 to Input 4 range is from -9999.9 to +9999.9;
o
For Input 5 to Input 8 range is from -70.0 to +300.0 degF or -55.0 to +150.0
degC;
High Threshold
- the high threshold for the measured value:
o
For Input 1 to Input 4 range is from -9999.9 to +9999.9;