Figure 7.24.
Inverse mode: AI Threshold 1 < AI Threshold 2
Pulse, ms (x100)
– if set to non-zero, the Relay operates in pulse mode. The
pulse duration is set in tenths of second (for example value of 20 means 2
seconds). The range is from 0 and 65535 (0 disables the pulse mode). When
enabled, each time the Relay is switched On, it will generate a single pulse
with specified duration.
The Relay can generate pulses only
if it‟s Working Mode=Multiple.
The Relay can be switched On/Off by “attached” Digital or Analog Input,
SNMP or HTTP/XML/JSON command, Week Schedule, and manually from
Web Monitoring & Control page.
At any time the pulse is active the Relay can be switched back Off by
“attached” Digital or Analog Input, SNMP or HTTP/XML/JSON command,
Week Schedule, and manually from Web Monitoring & Control page.
Disable Week Schedule
- enables/disables globally the week schedule
control for this Relay. This means the Relay may be in the schedule, but if this
flag is checked, then it won't be activated by the schedule.
7.12. Analog Outputs
Figure 7.25.
Analog Outputs page
Description
- identification string (max 7 chars);
This description will appear in XML/JSON files, as well as in the Monitoring &
Control page.
Units (0..1023)
– Analog Output value (0 to 1023 corresponds to a linear scale
of 0V DC to 10V DC).