09 Mar 2018
- 59 -
9. SNMP
9.1. SNMP Agent
smartDEN IP-Maxi
supports SNMPv2c protocol - operations get, get-next, get-
bulk, set. The provided SNMP commands are described in the
smartDEN IP-Maxi
file. Most of the parameters can be read/configured by SNMP. Two community
strings are used:
Read-only
for reading and
Read-write
for setting new values of the
parameters. The description of the parameters, grouped by their functions is given in
the next tables. Note that to obtain a valid OID number
„
x
‟ symbol should be replaced
by prefix
.1.3.6.1.4.1.42505
.
9.1.1.
Product
Table 9.1
.
Product
OID
Description
Access Syntax
x.
8.1.1.0
Device Name
R/W
DisplayString (SIZE(0..14))
x.
8.1.2.0
Firmware version
R
DisplayString
x.
8.1.3.0
Firmware build date
R
DisplayString
9.1.2.
Setup
Table 9.2
.
Digital Inputs
Start OID
End OID
Description
Access Syntax
x.
8.2.1.1.2.0
x.
8.2.1.1.2.7
Digital Input Description
R/W
DisplayString (SIZE(0..7))
x.
8.2.1.1.3.0
x.
8.2.1.1.3.7
Digital Input Counter
R/W
Counter32 (0..4294967295)
x.
8.2.1.1.4.0
x.
8.2.1.1.4.7
Digital Input Filter, ms
R/W
Integer (0..200)
x.
8.2.1.1.5.0
x.
8.2.1.1.5.7
Digital Input Trap Enable Flag
R/W
Integer { No(0), Yes(1) }
x.
8.2.1.1.6.0
x.
8.2.1.1.6.7
Digital Input Trap Value
R/W
Integer { Off(0), On(1), Both(2) }
x.
8.2.1.1.7.0
x.
8.2.1.1.7.7
Digital Input State
R
Integer { Off(0), On(1) }
Table 9.3
.
Analog Inputs
Start OID
End OID
Description
Access Syntax
x.
8.2.2.1.2.0
x.
8.2.2.1.2.7
Analog Input Description
R/W
DisplayString (SIZE(0..7))
x.
8.2.2.1.3.0
x.
8.2.2.1.3.7
Analog Input Trap LowThreshold
R/W
Integer (-9999..9999)
x.
8.2.2.1.4.0
x.
8.2.2.1.4.7
Analog Input Trap HighThreshold R/W
Integer (-9999..9999)
x.
8.2.2.1.5.0
x.
8.2.2.1.5.7
Analog Input Trap Enable Flag
R/W
Integer { No(0), Yes(1) }
x.
8.2.2.1.6.0
x.
8.2.2.1.6.7
Analog Input ADC Value
R
Integer (0..1023)
x.
8.2.2.1.7.0
x.
8.2.2.1.7.7
Analog Input Min Value
R/W
DisplayString (SIZE(0..7))
x.
8.2.2.1.8.0
x.
8.2.2.1.8.7
Analog Input Max Value
R/W
DisplayString (SIZE(0..7))
x.
8.2.2.1.9.0
x.
8.2.2.1.9.7
Analog Input Label
R/W
DisplayString (SIZE(0..3))
x.
8.2.2.1.10.0
x.
8.2.2.1.10.7 Analog Input Measured Value
R
DisplayString