Chapter 8 Optional Cards
MS300 (IP66 / NEMA 4X)
8-8
Operation / Storage
Operation
:
-10–50
°C (temperature), 90
% (humidity)
Storage
:
-25–70
°C (temperature), 95
% (humidity)
Shock / Vibration resistance
International standards
:
IEC 61800-5-1,
IEC 60068-2-6 / IEC 61800-5-1,
IEC 60068-2-27
MS300 (IP66 / NEMA 4X) Communication Parameters when Connected to EtherNet
When you connect the MS300 (IP66 / NEMA 4X) to EtherNet, set up the communication parameters based
on the table below. The EtherNet master can read and write frequency command words and operation command
words for the MS300 (IP66 / NEMA 4X) after you set the communication parameters.
Parameter
Function
Current Set Value
Definition of Parameter Values
00-20
Frequency command
source
8
The frequency command is controlled by
communication card.
00-21
Operation command
source
5
The operation command is controlled by
communication card.
09-30
Decoding method for
communication
0
Decoding method for the Delta AC motor
drive.
09-75
IP setting
0
Static IP(0) / Dynamic distribution IP(1)
09-76
IP address 1
192
IP address 192.168.1.5
09-77
IP address 2
168
IP address 192.168.1.5
09-78
IP address 3
1
IP address 192.168.1.5
09-79
IP address 4
5
IP address 192.168.1.5
09-80
Netmask 1
255
Netmask 255.255.255.0
09-81
Netmask 2
255
Netmask 255.255.255.0
09-82
Netmask 3
255
Netmask 255.255.255.0
09-83
Netmask 4
0
Netmask 255.255.255.0
09-84
Default gateway 1
192
Default gateway 192.168.1.1
09-85
Default gateway 2
168
Default gateway 192.168.1.1
09-86
Default gateway 3
1
Default gateway 192.168.1.1
09-87
Default gateway 4
1
Default gateway 192.168.1.1
Basic Registers
BR#
R/W
Content
Set Value
#0
R
Model name
Defined by the system. The model code of CMM-MOD01=H’0103.
#1
R
Firmware version
Displays the current firmware version in hex, e.g. H`0100 indicates
firmware version V1.00.
#2
R
Release date of the
version
Displays the date in decimal form. 10,000s digit and 1,000s digit are
for “month”; 100s digit and 10s digit are for “day”.
For 1 digit: 0 = AM; 1 = PM.
#11
R/W Modbus Time-out
Pre-defined setting: 500 (ms)
#13
R/W Keep Alive Time
Pre-defined setting: 30 (s)
LED Indicator & Troubleshooting
LED Indicators
LED
Status
Indication
Corrective Action
POWER
Green
On
Power supply in normal status
No action is required
Green
Off
No power supply
Check the power supply
Summary of Contents for Compact Drive MS300 IP66/NEMA 4X Series
Page 3: ......
Page 10: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 3 1 2 Model Name 1 3 Serial Number...
Page 18: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 11 This page intentionally left blank...
Page 24: ...Chapter 2 Dimensions MS300 IP66 NEMA 4X 2 6 This page intentionally left blank...
Page 28: ...Chapter 3 Installation MS300 IP66 NEMA 4X 3 4 This page intentionally left blank...
Page 29: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 32: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 4 4 2 Wiring Figure 4 2...
Page 34: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 6 This page intentionally left blank...
Page 83: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 33 The drive with MKMX SWA...
Page 85: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 35 The drive with MKMX SWB...
Page 87: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 37 The drive with MKMX SWC...
Page 126: ...Chapter 10 Digital Keypad MS300 IP66 NEMA 4X 10 8 This page intentionally left blank...