Chapter 7 Optional Accessories
MS300 (IP66 / NEMA 4X)
7-16
Length of the Motor Cable
1. Leakage current affects the motor and remedies
Due to larger parasitic capacitances in longer motor cables, longer cables increase the leakage
current. This can activate the over-current protection and display the incorrect current. In the worst
case, it can damage the drive.
If more than one motor is connected to the AC motor drive, the total motor cable length is the sum of
the cable length from AC motor drive to each motor.
For 460V series AC motor drives, when an overload relay is installed between the drive and the motor
to protect the motor from overheating, the connecting cable must be shorter than 50 m.
However, the overload relay could still malfunction. To prevent this, install an AC output reactor
(optional) to the drive and/or lower the carrier frequency setting (Pr.00-17).
2. Surge voltage affects the motor and remedies
When a PWM signal from an AC motor drive drives the motor, the motor terminals can easily
experience surge voltages (dv/dt) due to IGBT switching and cable capacitance. When the motor
cable is very long (especially for the 460V series), surge voltages (dv/dt) may reduce motor insulation
quality. To prevent this situation, follow the rules listed below.
a. Use a motor with enhanced insulation.
b. Connect an output reactor (optional) to the output terminals of the AC motor drive.
c. Reduce the motor cable length to the values in the table below.
The suggested motor shielded cable length in the following table complies with IEC 60034-17,
which is suitable for motors with a rated voltage ≤ 500 V
AC
and with an insulation level of ≥ 1.35 kV
p-p
460V Three-phase
Model
Without AC Reactor
With AC Reactor
Shielded Cable
[meter]
Non-shielded
Cable [meter]
Shielded Cable
[meter]
Non-shielded
Cable [meter]
VFD1A5MS43MNSAA
VFD1A5MS43MFSAA
35
50
50
90
VFD2A7MS43MNSAA
VFD2A7MS43MFSAA
35
50
50
90
VFD4A2MS43MNSAA
VFD4A2MS43MFSAA
35
50
50
90
VFD5A5MS43MNSAA
VFD5A5MS43MFSAA
50
75
75
115
VFD9A0MS43MNSAA
VFD9A0MS43MFSAA
50
75
75
115
VFD13AMS43MNSAA
VFD13AMS43MFSAA
50
75
75
115
VFD17AMS43MNSAA
VFD17AMS43MFSAA
100
150
150
225
Summary of Contents for Compact Drive MS300 IP66/NEMA 4X Series
Page 3: ......
Page 10: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 3 1 2 Model Name 1 3 Serial Number...
Page 18: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 11 This page intentionally left blank...
Page 24: ...Chapter 2 Dimensions MS300 IP66 NEMA 4X 2 6 This page intentionally left blank...
Page 28: ...Chapter 3 Installation MS300 IP66 NEMA 4X 3 4 This page intentionally left blank...
Page 29: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 32: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 4 4 2 Wiring Figure 4 2...
Page 34: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 6 This page intentionally left blank...
Page 83: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 33 The drive with MKMX SWA...
Page 85: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 35 The drive with MKMX SWB...
Page 87: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 37 The drive with MKMX SWC...
Page 126: ...Chapter 10 Digital Keypad MS300 IP66 NEMA 4X 10 8 This page intentionally left blank...