Chapter 8 Optional Cards
MS300 (IP66 / NEMA 4X)
8-16
Operation / Storage
Operation: -10–50 °C (temperature), 90 % (humidity)
Storage: -25–70 °C (temperature), 95 % (humidity)
Shock / Vibration resistance International standard:
IEC 61800-5-1, IEC 60068-2-6 / IEC 61800-5-1, IEC 60068-2-27
Installation
Connecting the CMM-EIP01 to the Network
1. Switch off the power supply.
2. Open the front cover of the drive.
3. Connect the CAT-5e network cable to the RJ45 port on the
CMM-EIP01 (as shown in the right figure).
RJ45 PIN Definition
PIN
Signal
Definition
PIN
Signal
Definition
1
Tx+
Data transmit positive
5
--
N/C
2
Tx-
Data transmit negative
6
Rx-
Data receive negative
3
Rx+
Data receive positive
7
--
N/C
4
--
N/C
8
--
N/C
MS300 (IP66 / NEMA 4X) Communication Parameters when Connected to EtherNet
When you connect the MS300 (IP66 / NEMA 4X) to EtherNet, set up the communication
parameters based on the table below. The EtherNet master can read and write the frequency
command words and operation command words for the MS300 (IP66 / NEMA 4X) after you set the
communication parameters.
Parameter
Function
Current Set Value
Definition of Parameter Values
00-20
Frequency command
source
8
The frequency command is controlled by
the communication card.
00-21
Operation command
source
5
The operation command is controlled by
the communication card.
09-30
Decoding method for
communication
0
The decoding method for Delta AC motor
drive.
09-75
IP setting
0
Static IP(0) / Dynamic distribution IP(1)
09-76
IP address 1
192
IP address 192.168.1.5
09-77
IP address 2
168
IP address 192.168.1.5
09-78
IP address 3
1
IP address 192.168.1.5
09-79
IP address 4
5
IP address 192.168.1.5
09-80
Netmask 1
255
Netmask 255.255.255.0
09-81
Netmask 2
255
Netmask 255.255.255.0
09-82
Netmask 3
255
Netmask 255.255.255.0
09-83
Netmask 4
0
Netmask 255.255.255.0
09-84
Default gateway 1
192
Default gateway 192.168.1.1
09-85
Default gateway 2
168
Default gateway 192.168.1.1
09-86
Default gateway 3
1
Default gateway 192.168.1.1
09-87
Default gateway 4
1
Default gateway 192.168.1.1
Summary of Contents for Compact Drive MS300 IP66/NEMA 4X Series
Page 3: ......
Page 10: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 3 1 2 Model Name 1 3 Serial Number...
Page 18: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 11 This page intentionally left blank...
Page 24: ...Chapter 2 Dimensions MS300 IP66 NEMA 4X 2 6 This page intentionally left blank...
Page 28: ...Chapter 3 Installation MS300 IP66 NEMA 4X 3 4 This page intentionally left blank...
Page 29: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 32: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 4 4 2 Wiring Figure 4 2...
Page 34: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 6 This page intentionally left blank...
Page 83: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 33 The drive with MKMX SWA...
Page 85: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 35 The drive with MKMX SWB...
Page 87: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 37 The drive with MKMX SWC...
Page 126: ...Chapter 10 Digital Keypad MS300 IP66 NEMA 4X 10 8 This page intentionally left blank...