Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-3
Parameter
Functions
Settings
Factory
Setting
Customer
43: HPF3 (OC hardware error)
44: HPF4 (OV hardware error)
45: CF3.3 (U-phase error)
46: CF3.4 (V-phase error)
47: CF3.5 (W-phase error)
48: CF3.6 (OV or LV)
49: CF3.7 (Isum error)
50: CF3.8 (Temperature sensor error)
00-02
AC Drive Status
Indication 2
Bit 0~1: 00: Run led is off and stop led is on.
01: Run led is blink and stop led is
on.
10: Run led is on and stop led is
blink.
11: Run led is on and stop led is off.
Bit 2: 1: Jog on.
Bit 3~4: 00: Rev led is off and FWD led is on.
01: Rev led is blink and FWD led is
on.
10: Rev led is on and FWD led is
blink.
11: Rev led is on and FWD led is off.
Bit 5-7: Reserved
Bit 8: Master frequency source via
communication interface
Bit 9: Master frequency source via analog
Bit10: Running command via communication
interface
Bit11: Parameter locked
Bit12~15: Reserved
Read
00-03
Frequency Setting (F)
or Closed Loop
Control Setting Point
Read only
Read
00-04
Output Frequency (H) Read only
Read
00-05
Output Current (A)
Read only
Read
00-06
DC-BUS Voltage (U)
Read only
Read
00-07
Output Voltage (E)
Read only
Read
00-08 Output
Power
Factor
(n)
Read only
Read
00-09
Output Power (kW)
Read only
Read
00-10 Feedback
Signal
Actual Value
Read only
Read
00-11
Feedback Signal (%) Read only
Read
00-12
User Target Value
(Low bit) uL 0-99.99
Read only
Read