B.4.2 AC Output Reactor Recommended Value
460V, 50/60Hz, 3-Phase
Inductance (mh)
kW HP
Fundamental
Amps
Max. continuous
Amps
3% Impedance
5% Impedance
0.75 1
4
6
9
12
1.5 2
4
6
6.5
9
2.2 3
8
12
5
7.5
3.7 5
12
18
2.5
4.2
5.5 7.5
18
27
1.5
2.5
7.5 10
18
27
1.5
2.5
11 15
25
37.5
1.2
2
15 20
35
52.5
0.8
1.2
18.5 25
45
67.5
0.7
1.2
22 30
45
67.5
0.7
1.2
30 40
80
120
0.4
0.7
37 50
80
120
0.4
0.7
45 60
100
150
0.3
0.45
55 75
130
195
0.2
0.3
75 100
160
240
0.15
0.23