Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-13
Parameter
Functions
Settings
Factory
Setting
Customer
31: FF12 (Fan 1, 2 Fault)
32: FF13 (Fan 1, 3 Fault)
33: FF23 (Fan 2, 3 Fault)
34: Fv (Gate Drive Low Voltage Protect)
35~40: Reserved
41: HPF1 (GFF hardware error)
42: HPF2 (CC,OC hardware error)
43: HPF3 (OC hardware error)
44: HPF4 (OV hardware error)
45: CF3.3 (U-phase error)
46: CF3.4 (V-phase error)
47: CF3.5 (W-phase error)
48: CF3.6 (OV or LV)
49: CF3.7 (Isum error)
50: CF3.8 (Temperature sensor error)
06-15 Parameter
Reset
00~65535
09: Reset parameters (50Hz, 380)
10: Reset parameters (60Hz, 440)
00
06-16 Parameter
Protection
Password Input
00~65535 00
06-17 Parameter
Protection
Password Setting
00~65535
00: No password protection
00
Group 7 AC Drive and Motor Parameters
Parameter
Functions
Settings
Factory
Setting
Customer
07-00
Identity Code of AC
Drive
Display by model type
##
07-01
Rated Current of AC
Drive
Display by model type
##
07-02 Full-load Current of
Motor
30~120% 100%
07-03 No-load Current of
Motor
1~99% 30%
07-04 Auto
Slip
Compensation Gain
0.0~3.0 0.0
07-05
Rated Slip Frequency
of Motor
0.00~20.00Hz 0.00
07-06 Auto
Torque
Compensation Gain
0.0~10.0 0.0
07-07 Torque
Compensation
Gain by Manually
0.0~10.0 0.0