Chapter 4 Parameters
|
4-24
Revision July 2008, EG03, SW V1.06
Code
AC Drive Status
Explanation
22
PHL (phase loss)
Input power lacks phase.
3-phase input power is unbalance and exceeds
specification.
23
Lc (Low Current)
Low current detection during operation.
24
FbL(Feedback Loss)
Feedback signal is abnormal.
25 Reserved
26
FANP
Fan Power Fault
27
FF1
Fan 1 Fault
28
FF2
Fan 2 Fault
29
FF3
Fan 3 Fault
30
FF123
Fan 1, 2, 3 Fault
31
FF12
Fan 1, 2 Fault
32
FF13
Fan 1, 3 Fault
33
FF23
Fan 2, 3 Fault
34
Fv
Gate Drive Low Voltage Protect
35~40 Reserved
41
HPF1
GFF hardware error
42
HPF2
CC,OC hardware error
43
HPF3
OC hardware error
44
HPF4
OV hardware error
45
CF3.3
U-phase error
46
CF3.4
V-phase error
47
CF3.5
W-phase error
48
CF3.6
OV or LV
49
CF3.7
Isum error
50
CF3.8
Temperature sensor error
00 - 02
AC Drive Status Indication 2
Factory setting: Read Only
Display
Bit 0~1: 00: Run LED is off and stop led is on. (AC Drive stopping)
01: Run LED is blink and stop led is on. (AC Drive deceleration to
stop)
10: Run LED is on and stop led is blink. (AC Drive standby)
11: Run LED is on and stop led is off. (AC Drive running)
Bit 2: 1: Jog on.
Bit 3~4: 00: Rev LED is off and FWD led is on. (Forward)
01: Rev LED is blink and FWD led is on. (Reverse to Forward)
10: Rev LED is on and FWD led is blink. (Forward to Reverse)
11: Rev LED is on and FWD led is off. (Reverse)
Bit 5-7: Reserved