Chapter 4 Parameters
|
4-4
Revision July 2008, EG03, SW V1.06
Parameter
Functions
Settings
Factory
Setting
Customer
00-13
User Target Value
(High bit) uH 0-9999
Read only
Read
00-14
PLC Time
Read only
Read
00-15 Output
Reactive
Power (KVAR)
Read only
Read
Group 1 Basic Parameters
Parameter
Functions
Settings
Factory
Setting
Customer
01-00 Maximum
Output
Frequency
50.00~160.00Hz 60.00
01-01 Maximum
Voltage
Frequency
(Base Frequency)
0.10~160.00 Hz
60.00
01-02 Maximum
Output
Voltage
0.2V ~ 510.0V
440.0
01-03
Mid-point Frequency 0.10~120 Hz
3.00
01-04 Mid-point
Voltage 0.2V~510.0V
11.0
01-05 Minimum
Output
Frequency
0.10~20.00 Hz
3.00
01-06 Minimum
Output
Voltage
0.2V~100.0V 11.0
01-07 Upper
Bound
Frequency
0.00~160.00 Hz
60.00
01-08 Lower
Bound
Frequency
0.00~160.00 Hz
0.00
01-09 Acceleration Time 1
0.1~3600.0 Sec
10.0/
60.0
01-10 Deceleration Time 1
0.1~3600.0 Sec
10.0/
60.0
01-11 Acceleration Time 2
0.1~3600.0 Sec
10.0/
60.0
01-12 Deceleration Time 2
0.1~3600.0 Sec
10.0/
60.0
01-13 Acceleration Time 3
0.1~3600.0 Sec
10.0/
60.0
01-14 Deceleration Time 3
0.1~3600.0 Sec
10.0/
60.0
01-15 Acceleration Time 4
0.1~3600.0 Sec
10.0/
60.0
01-16 Deceleration Time 4
0.1~3600.0 Sec
10.0/
60.0
Summary of Contents for AC Motor Drive VFD-G
Page 1: ......
Page 2: ......
Page 3: ......
Page 141: ...Chapter 4 Parameters 4 90 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...