Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-11
Parameter
Functions
Settings
Factory
Setting
Customer
05-20
Time Duration Step 4
0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-21
Time Duration Step 5
0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-22
Time Duration Step 6
0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-23
Time Duration Step 7
0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-24
Time Duration Step 8
0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-25
Time Duration Step 9
0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-26
Time Duration Step 10 0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-27
Time Duration Step 11 0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-28
Time Duration Step 12 0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-29
Time Duration Step 13 0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-30
Time Duration Step 14 0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-31
Time Duration Step 15 0.0 to 65500 Sec / 0.0~6550.0 Sec
0.0
05-32
Time Unit Settings
00: 1 Sec
01: 0.1 Sec
00
Group 6 Protection Function Parameters
Parameter
Functions
Settings
Factory
Setting
Customer
06-00 Over-voltage
Stall
Prevention
660.0V~820.0VDC
00: Disabled
780.0
06-01 Over-current
Stall
Prevention during
Acceleration
20~250%
00: Disabled
150%
06-02 Over-current
Stall
Prevention during
operation
20~250%
00: Disabled
150%
06-03 Over-torque
Detection
Selection
00: Over-torque detection disabled.
01: Over-torque detection enabled during
constant speed operation (OL2), and
operation continues.
02: Over-torque detection enabled during
constant speed operation (OL2), and
operation halted.
03: Over-torque detection enabled during
operation (OL2), and operation
continues.
04: Over-torque detection enabled during
operation (OL2), and operation halted.
00
06-04 Over-torque
Detection
Level
30~150% 110
06-05 Over-torque
Detection
Time
0.1~60.0 Sec
0.1