Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-5
Parameter
Functions
Settings
Factory
Setting
Customer
01-17 JOG
Acceleration
Time
0.1~3600.0 Sec
10.0/
60.0
01-18 JOG
Deceleration
Time
0.1~3600.0 Sec
10.0/
60.0
01-19 JOG Frequency
0.0 Hz~160.00 Hz
6.00
01-20
S Curve Delay Time
in Accel
0.00~2.50sec
0.00
01-21
S Curve Delay Time
in Decel
0.00~2.50sec
0.00
01-22 Modulation
Index
0.90~1.20
1.00
01-23
Accel/Decel Time Unit 00: Unit is 1 Sec
01: Unit is 0.1 Sec
02: Unit is 0.01 Sec
01
Group 2 Operation Method Parameters
Parameter
Functions
Settings
Factory
Setting
Customer
02-00 Source of Frequency
Command
00: via keypad
01: via analog input AI1
02: via analog input AI2
03: via RS485 serial communication
04: via External Reference
00
02-01 Source of Operation
Command
00: Controlled by the digital keypad
01: Controlled by the external terminals,
keypad STOP enabled.
02: Controlled by external terminals, keypad
STOP disabled.
03: Controlled by the RS-485 communication
interface, keypad STOP enabled.
04: Controlled by the RS-485 communication
interface, keypad STOP disabled.
00
02-02
Stop Method
00: Stop = ramp to stop, E.F. (External Fault)
= coast to stop
01: Stop = coast to stop, E.F. = coast to stop
02: Stop = ramp to stop, E.F. = ramp to stop
03: Stop = coast to stop, E.F. = ramp to stop
00
02-03 PWM
Carrier
Frequency Selections
7.5~10HP: 4000~6000Hz
15~30HP: 3000~6000Hz
40~125HP: 2000~6000Hz
150~300HP: 2000~4000Hz
6000
6000
4000
4000