![Delphin Expert Logger Manual Download Page 270](http://html.mh-extra.com/html/delphin/expert-logger/expert-logger_manual_2471097270.webp)
Expert
Logger
Version
100
200
300
400
Maximum input frequency
250 Hz
Digital outputs (also
PWM)
4
4
1
0
Grouping
2 per group
Electrical values
Max. switching voltage/current
50 V/2.5 A
On-state resistance (Rds
on
)
0.11 Ω
Maximum power loss (P
tot
)
2.5 W
PWM
PWM basic frequency
5 Hz … 10 kHz
Duty cycle/resolution
1:1000
Galvanic isolation
Output to system/other channels/PE
±400 VDC
Output-to-output same group
No
Digital outputs (freq. /
PWM)
4
4
0
24
Grouping
2 per group
Input
Level
low
0 … 1 V
high
5 … 100 [email protected] mA
Debouncing
1 … 60000 µs
Digital input
Max. edge
change
32000 / s
Frequency input
Measuring
range
0.2 Hz … 1 MHz (100
kHz at EL100 / EL200 <
V1.3)
Minimum pulse
width
500 ns
Counter width
64 bit
Precision
0.01% of measurement
value
Resolution of frequency inputs
32-bit, time resolution 250 ns
Output
Electrical values
Max. switching
voltage/current
50 V/2.5 A
On-state res-
istance (Rds
on
)
0.11 Ω
Maximum
power loss (P
tot
)
2.5 W
PWM
PWM basic fre-
quency
5 Hz … 10 kHz
Duty cycle/res-
olution
1:1000
Galvanic isolation
Input to output/same
group
No
Input/output to sys-
tem/other channels/PE
±400 VDC
270
Delphin Technology AG
Januar 2018
Expert
Logger
Manual