If you want to create a sensor manually, deactivate the
automatic sensor
detection
and confirm the dialogue. After confirming the dialogue,
is
displayed as a symbol in the channel list for the
SDI 12
master.
New
SDI 12
sensors are usually configured for the address 0
by default. Note that a sensor connection is not possible if fur-
ther sensors of the same address are connected. In this case,
disconnect the sensors of the same address. Now connect one
of the sensors individually and change the sensor’s address
using the
SDI 12
sensor dialogue. Repeat this step until all
sensors have been connected.
Automatic sensor detection
To start
automatic sensor detection
once, please follow these steps:
1. Check the automatic sensor detection box (only needed once).
2. Select the address ranges in which you want to search for connected
sensors.
3. Select whether to automatically create measured value channels for newly
found sensors.
4. Confirm the dialogue.
Subsequently, channels are automatically created for sensors and – if
selected – channels are created for measured data.
Automatic sensor detection is automatically reset after execution and can
be reactivated as required.
Info
Automatic sensor detection can take up to three minutes
depending on the selected address ranges!
After confirming the dialogue,
is displayed as a symbol in the channel
list for the SDI-12 Master.
4.12.1.2
SDI 12 Sensor
Create a channel for a
SDI 12
sensor via the context menu Create chan-
nel
→
SDI-12 Sensor of the
SDI 12
master.