Code
Display text Description
Adjustment range
Subme
nu
280
350
430
500
570
650
CP010
Tflow set
point zone
Zone flow temperature
setpoint, used when the
zone is set to a fixed flow
setpoint.
7 - 100 °C
Direct
zone
90
90
90
90
90
90
CP290
ConfigZone
PumpOut
Configuration of Zone
Pump Output
0 = Zone output
1 = CH mode
2 = DHW mode
3 = Cooling mode
4 = Error report
5 = Burning
6 = Service flag
7 = System error
8 = DHW looping
9 = Primary pump
10 = Buffer pump
Zone
disabled
Direct
zone
0
0
0
0
0
0
CP520
Zone Power
setpoint
Power setpoint per zone
0 - 100 %
Direct
zone
100
100
100
100
100
100
CP530
Zone PWM
Pump
speed
Pulse Width Modulation
pump speed per zone
20 - 100 %
Direct
zone
100
100
100
100
100
100
CP680
ConfPairing
RU Zone
Select the Bus channel of
the room unit for this zone
0 - 255
Direct
zone
0
0
0
0
0
0
DP003
Abs. max
fan DHW
Maximum fan speed on
Domestic Hot Water
1000 - 7000 Rpm
Gas
fired ap
pliance
5200 5500 3500 3800 4300 4100
DP010
Hysteresis
DHW
Temperature hysteresis
for the heat generator to
start on domestic hot wa
ter production
1 - 10 °C
Gas
fired ap
pliance
5,5
5,5
5,5
5,5
5,5
5,5
DP011
Stop offset
DHW
Temperature offset to stop
heat generator on domes
tic hot water production
0 - 100 °C
Gas
fired ap
pliance
5
5
5
5
5
5
DP020
Postrun
DHW
pump/3wv
Post run time of the DHW
pump/3 way valve after
DHW production
0 - 99 Sec
Gas
fired ap
pliance
10
10
10
10
10
10
DP140
DHW load
type
DHW load type (0 : Combi,
1 : Solo)
0 = Combi
1 = Solo
2 = Layered cylin
der
3 = Process heat
4 = External
Gas
fired ap
pliance
1
1
1
1
1
1
GP010
GPS Check Gas Pressure Switch
check on/off
0 = No
1 = Yes
Gas
fired ap
pliance
1
1
1
1
1
1
GP017
Max power
Maximum power percent
age in kilo Watt
0 - 1000 kW
Gas
fired ap
pliance
293,
9
353,
1
427,
1
496,
2
565,
9
642
GP022
Tfa Filter
Tau
Tau factor for average flow
temperature calculation
0 - 255
Gas
fired ap
pliance
1
1
1
1
1
1
GP042
Fan RPM
Max
Maximum fan speed
0 - 65535 Rpm
GVC
Pneu
matic
5700 5800 3700 4000 4500 4300
GP050
Power Min
Minimum power in kilo
Watt for RT2012 calcula
tion
0 - 300 kW
Gas
fired ap
pliance
54
68
82
95
109
122
10 Settings