Tab.93 Factory settings at basic installer level
Code
Display text
Description
Range
Submenu
Default
setting
AP074
Force summer
mode
The heating is stopped. Hot water is
maintained. Force Summer Mode
0 = Off
1 = On
Outdoor
temperature
0
AP077
Max. display level Maximum Level of parameters and
signals to display on MK
1 = End user
2 = Installer
3 = Installer advanced
4 = Lab
5 = Controls Development
System
Functionality
3
AP081
Device short
name
Shortname of the device
System
Functionality
S10
AP089
Installer name
Name of the installer
Mandatory
bus master
AP090
Installer phone
Telephone number of the installer
Mandatory
bus master
CP010
CP011
CP012
CP013
CP014
Tflow setpoint
zone
Zone flow temperature setpoint, used
when the zone is set to a fixed flow
setpoint.
7 °C - 100 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
75
40
75
40
75
CP080
CP081
CP082
CP083
CP084
CP085
User T.Room
Activity
Room setpoint temperature of the
user zone activity
5 °C - 30 °C
CIRCA 1
16
20
6
21
22
23
CP086
CP087
CP088
CP089
CP090
CP091
User T.Room
Activity
Room setpoint temperature of the
user zone activity
5 °C - 30 °C
CIRCB 1
16
20
6
21
22
23
CP092
CP093
CP094
CP095
CP096
CP097
User T.Room
Activity
Room setpoint temperature of the
user zone activity
5 °C - 30 °C
DHW 1
16
20
6
21
22
23
CP098
CP099
CP100
CP101
CP102
CP103
User T.Room
Activity
Room setpoint temperature of the
user zone activity
5 °C - 30 °C
CIRCC 1
16
20
6
21
22
23
CP104
CP105
CP106
CP107
CP108
CP109
User T.Room
Activity
Room setpoint temperature of the
user zone activity
5 °C - 30 °C
AUX 1
16
20
6
21
22
23
CP140
CP141
CP142
CP143
CP144
CP145
RoomCoolTempS
etpoint
Setpoint of the room cooling
temperature of the zone
20 °C - 30 °C
CIRCA 1
30
25
25
25
25
25
10 Settings
104
C 340 / C 640