Tab.91 Factory settings at installer level
Code
Display text
Description
Range
Subme
nu
Default
setting
EP018
Status relay func.
Status relay function
0 = No Action
1 = Alarm
2 = Alarm Inverted
3 = Burning
4 = Not burning
5 = Reserved
6 = Reserved
7 = Service request
8 = Boiler on CH
9 = Boiler on DHW
10 = CH pump on
11 = Locking or Blocking
12 = Cooling mode
Status
informati
on
0
EP019
Status relay func.
Status relay function
0 = No Action
1 = Alarm
2 = Alarm Inverted
3 = Burning
4 = Not burning
5 = Reserved
6 = Reserved
7 = Service request
8 = Boiler on CH
9 = Boiler on DHW
10 = CH pump on
11 = Locking or Blocking
12 = Cooling mode
Status
informati
on
0
EP028
Function 10V-
PWM
Selects the function of the 0-10 Volt
output
0 = 0-10V 1 (Wilo)
1 = 0-10V 2 (Gr. GENI)
2 = PWM signal (Solar)
3 = 0-10V 1 limited
4 = 0-10V 2 limited
5 = PWM signal limited
6 = PWM signal (UPMXL)
0-10 volt
or PWM
out
0
EP029
Source 10V-PWM Selects the source signal for the 0-10
Volt output
0 = PWM
1 = Requested power
2 = Actual power
0-10 volt
or PWM
out
0
10.3.4 SCB-10 expansion PCB settings
Important
The table shows the factory setting for the parameters.
Tab.92 Navigation for basic installer level
Level
Menu path
Basic installer
> Installation Setup > SCB-10 > Submenu
> Parameters, counters, signals > Parameters
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
10 Settings
7762666 - v.02 - 29092020