![DeDietrich C 340 280 Installation And User Manual Download Page 80](http://html1.mh-extra.com/html/dedietrich/c-340-280/c-340-280_installation-and-user-manual_2462417080.webp)
Tab.73 Parameter settings
Code
Display text
Advice
EP018
EP019
Status relay func.
Configure the function of the status contacts.
0 = No Action : The status contact (C-Nc) will do nothing.
1 = Alarm : The status contact (C-No) will close when there is an error.
2 = Alarm Inverted : The status contact (C-No) is closed when there is no error.
3 = Generator on : The status contact (C-No) will close when the appliance is in
operation.
4 = Generator off : The status contact (C-No) is closed when the appliance is
not in operation.
5 = Reserved : This option is not available.
6 = Reserved : This option is not available.
7 = Service request : The status contact (C-No) will close when service is re
quested.
8 = Generator on CH : The status contact (C-No) will close when the appliance
is active for central heating mode.
9 = Generator on DHW : The status contact (C-No) will close when the appli
ance is active for domestic hot water mode.
10 = CH pump on : The status contact (C-No) will close when the system pump
runs.
11 = Locking or Blocking : The status contact (C-No) will close when a locking
or blocking is active.
12 = Cooling mode : The status contact (C-No) will closes when the appliance is
active for cooling.
(1) EP019 is only available on devices with two status contacts.
9.3
Commissioning the installation
The commissioning menu shows submenus and tests needed for the
commissioning of the appliance.
1. Press the button.
2. Select Commissioning Menu.
3. Select the submenu with settings you want to change or the test you
want to perform.
9.3.1
Chimney sweep menu
Select the tile [ ] to open the chimney sweep menu. The Change load
test mode menu will appear:
A Change load test mode
B Load test mode
Tab.74 Load tests in the chimney sweep menu
Change load test mode
Settings
Off
No test
Low power
Part load test
Medium power
Full load test for Central Heating mode
High power
Full load test for Central H Domestic Hot Water mode
Fig.91
Load test
AD-3000941-03
..... ... ....... .... .. ..... ....
.........
..... ... ....... ....
..... ... ....... ....
....... .... .. ..... ....
.......
....... ...........
......
.....
...
.....
..... ... ....... .... .. ..... ....... .... ..... .......
i
.....
....... .... ....... .... .......
.... ...... ....
... ......
11:20
A
B
9 Installer instructions
80
C 340 / C 640
7762666 - v.02 - 29092020