Code
Display text
Description
Range
Submenu
Default
setting
CP480
CP481
CP482
CP483
CP484
ScreedStartTemp Setting of the start temperature of the
screed drying program of the zone
20 °C - 50 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
20
20
20
20
20
CP490
CP491
CP492
CP493
CP494
ScreedStopTemp Setting of the stop temperature of the
screed drying program of the zone
20 °C - 50 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
20
20
20
20
20
CP500
CP501
CP502
CP503
CP504
Tflow Sensor
Enable
Enable/Disable Flow temperature
sensor of the zone
0 = Off
1 = On
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
0
0
0
CP560
CP561
CP562
CP563
CP564
ZoneConfigDHW
Antileg
Configuration of the Domestic Hot
Watter Antilegionnella Protection of
the zone
0 = Disabled
1 = Weekly
2 = Daily
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
0
0
0
CP600
CP601
CP602
CP603
CP604
ProcessHeat Spt
zone
Heat demand setpoint during process
heat of zone
20 °C - 100 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
60
60
60
60
60
CP610
CP611
CP612
CP613
CP614
Hys PH on per
zone
Hysteresis switched on for process
heat per zone
1 °C - 15 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
6
6
6
6
6
CP620
CP621
CP622
CP623
CP624
Hys PH off per
zone
Hysteresis switched off for process
heat per zone
1 °C - 15 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
6
6
6
6
6
CP630
CP631
CP632
CP633
CP634
StartdayAntileg
zone
Startday of the function antilegionella
of the zone
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
6
6
6
6
6
CP640
CP641
CP642
CP643
CP644
OTH LogicLev
contact
Opentherm Logic level contact of the
zone
0 = Open
1 = Closed
2 = Off
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
1
1
1
1
1
CP650
CP651
CP652
CP653
CP654
RedRoomTempC
ool Zone
Desired reduced room temperature
setpoint in cooling mode per zone
20 °C - 30 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
29
29
29
29
29
CP690
CP691
CP692
CP693
CP694
RevContactOTH
cool
Reversed OpenTherm contact in
cooling mode for heat demand per
zone
0 = No
1 = Yes
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
0
0
0
10 Settings
110