Code
Display text
Description
Range
Submenu
Default
setting
EP035
Max Setp Volt
0-10V
Sets the maximum set point voltage
for 0 - 10 volts
0 V - 10 V
0-10 volt
input
10
EP046
Digital input
config
Sets the general configuration of the
digital input
0 = Stop h DHW
1 = Stop heating
2 = Stop DHW
3 = Forced setpoint
4 = Buffer Tank input
Digital Input
0
EP056
Logic level Digi In Sets the logic level contact of the
Smart Control Board digital input
0 = Open
1 = Closed
2 = Off
Digital Input
1
EP066
Req FlowSetp
digi In
Requested flow setpoint when digital
input is configured to forced heat
7 °C - 100 °C
Digital Input
80
EP076
Req PowSetp digi
In
Requested power setpoint when
digital input is configured to forced
heat
0 % - 100 %
Digital Input
100
NP005
Cascade
Permutation
Choice of the leading
generator,.AUTO: Switching of order
every 7 days
0 - 127
Cascade
management
B
0
NP006
Cascade Type
Cascading boilers by adding
successively or in parallel, the boilers
function simultaneously
0 = Traditional
1 = parallel
Cascade
management
B
0
NP007
CascTOutsideHe
atParl
Outdoor start temperature heating of
all stages in parallel mode
-10 °C - 20 °C
Cascade
management
B
10
NP008
CascTPostRunG
enePump
Duration of post operation of the
cascade generator pump
0 Min - 30 Min
Cascade
management
B
4
NP009
CascInterStageTi
me
Switch on and switch off timing for
the producer of the cascade
1 Min - 60 Min
Cascade
management
B
4
NP010
CascTOutsideCo
olPara
Outdoor start temperature cooling of
all stages in parallel mode
10 °C - 40 °C
Cascade
management
B
30
NP011
CascadeTypeAlg
o
Choice of Cascade Algorithm type,
power or temperature
0 = Temperature
1 = Power
Cascade
management
B
0
NP012
CascPowerRiseTi
me
Cascade, Time to reach Temperature
Septoint
1 = 10
Cascade
management
B
1
NP013
CascForceStop
Pprim
Force Primary Pump to Stop on
cascade
0 = No
1 = Yes
Cascade
management
B
0
NP014
Cascade Mode
Functionnement Mode of cascade :
automatic, heating or cooling
0 = Automatic
1 = Heating
2 = Cooling
Cascade
management
B
0
Tab.96 Navigation for advanced installer level
Level
Menu path
Advanced installer
> Installation Setup > SCB-10 > Submenu
> Parameters, counters, signals > Adv. Parameters
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
10 Settings
112