Code
Display text Description
Adjustment range
Subme
nu
560
700
860
1000 1140 1300
CP640
OTH Logi
cLev con
tact
Opentherm Logic level
contact of the zone
0 = Open
1 = Closed
2 = Off
Direct
zone
1
1
1
1
1
1
CP730
Zone Heat
up speed
Selection of heat up speed
of the zone
0 = Extra Slow
1 = Slowest
2 = Slower
3 = Normal
4 = Faster
5 = Fastest
Direct
zone
0
0
0
0
0
0
CP740
Zone cool
down speed
Selection of cool down
speed of the zone
0 = Slowest
1 = Slower
2 = Normal
3 = Faster
4 = Fastest
Direct
zone
0
0
0
0
0
0
CP780
Control
strategy
Selection of the control
strategy for the zone
0 = Automatic
1 = Room Temp.
based
2 = Outdoor Temp.
based
3 = Outdoor &
room based
Direct
zone
0
0
0
0
0
0
EP014
SCB func.
10V PWMin
Smart Control Board func
tion 10 Volt PWM input
0 = Off
1 = Temperature
control
2 = Power control
0-10 volt
input
0
0
0
0
0
0
GP007
Fan RPM
Max CH
Maximum fan speed dur
ing Central Heating mode
1000 - 8500 Rpm
Gas
fired ap
pliance
5200 5500 3500 3800 4300 4100
GP008
Fan RPM
Min
Minimum fan speed during
Central H Domes
tic Hot Water mode
900 - 8500 Rpm
Gas
fired ap
pliance
GVC
Pneu
matic
1900 1850 1300 1250 1400 1350
GP009
Fan RPM
Start
Fan speed at appliance
start
900 - 5000 Rpm
Gas
fired ap
pliance
GVC
Pneu
matic
2500 2500 1400 1400 1500 1600
GP010
GPS Check Gas Pressure Switch
check on/off
0 = No
1 = Yes
Gas
fired ap
pliance
1
1
1
1
1
1
GP021
Temp diff
Modulating
Modulate back when delta
temperature is large then
this treshold
5 - 25 °C
Gas
fired ap
pliance
25
25
25
25
25
25
PP015
CH Pump
postrun time
Central heating pump post
run time
1 - 99 Min
Gas
fired ap
pliance
3
3
3
3
3
3
PP016
Max. CH
pump speed
Maximum central heating
pump speed (%)
20 - 100 %
Gas
fired ap
pliance
100
100
100
100
100
100
PP018
Min CH
pump speed
Minimum central heating
pump speed (%)
20 - 100 %
Gas
fired ap
pliance
20
20
20
20
20
20
PP023
CH Hystere
sis
Temperature hysteresis
for the generator to start
on central heating
1 - 25 °C
Gas
fired ap
pliance
10
10
10
10
10
10