![DeDietrich C 340 280 Installation And User Manual Download Page 111](http://html1.mh-extra.com/html/dedietrich/c-340-280/c-340-280_installation-and-user-manual_2462417111.webp)
Code
Display text
Description
Range
Submenu
Default
setting
CP700
CP701
CP702
CP703
CP704
DHW Cal Offset
zone
Offset for calorifier sensor per zone
0 °C - 30 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
0
0
0
CP710
CP711
CP712
CP713
CP714
Zone
IncTFlowStp
DHW
Increase primary temperature
setpoint for heating DHW calorifier of
the zone
0 °C - 40 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
20
20
20
20
20
CP720
CP721
CP722
CP723
CP724
Zone, IncFT
ProcHeat
Increase Primary Temperature
setpoint for process heat calorifier of
the zone
0 °C - 40 °C
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
20
20
20
20
20
CP750
CP751
CP752
CP753
CP754
MaxZone Preheat
time
Maximum zone preheat time
0 Min - 240 Min
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
0
0
0
CP760
CP761
CP762
CP763
CP764
Zone DHW TAS
enable
The calorifier of the zone is equipped
with a Titan Active System anode
0 = No
1 = Yes
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
1
0
0
CP780
CP781
CP782
CP783
CP784
Control strategy
Selection of the control strategy for
the zone
0 = Automatic
1 = Room Temp. based
2 = Outdoor Temp. based
3 = Outdoor & room based
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
0
0
0
EP014
SCB func. 10V
PWMin
Smart Control Board function 10 Volt
PWM input
0 = Off
1 = Temperature control
2 = Power control
0-10 volt
input
0
EP018
Status relay func. Status relay function
0 = No Action
1 = Alarm
2 = Alarm Inverted
3 = Burning
4 = Not burning
5 = Reserved
6 = Reserved
7 = Service request
8 = Boiler on CH
9 = Boiler on DHW
10 = CH pump on
11 = Locking or Blocking
12 = Cooling mode
Status
information
11
EP030
Min Setp Temp
0-10V
Sets the minimum set point
temperature for 0 - 10 volts for the
Smart Control Board
0 °C - 100 °C
0-10 volt
input
0
EP031
Max Setp Temp
0-10V
Sets the maximum set point
temperature for 0 - 10 volts for the
Smart Control Board
0.5 °C - 100 °C
0-10 volt
input
100
EP032
Min Setp Power
0-10V
Sets the minimum set point power for
0 - 10 volts for the Smart Control
Board
0 % - 100 %
0-10 volt
input
0
EP033
Max Setp Power
0-10V
Sets the maximum set point power
for 0 - 10 volts
5 % - 100 %
0-10 volt
input
100
EP034
Min Setp Volt
0-10V
Sets the minimum set point voltage
for 0 - 10 volts for the Smart Control
Board
0 V - 10 V
0-10 volt
input
0.5
10 Settings
7762666 - v.02 - 29092020
C 340 / C 640