58
Outputs to be controlled (on/off) based on the state of this input. The two output types allowed are relays (both
physical and virtual) and SNMP SETs. For the relays, adding a P suffix will Pulse the relay (ex: 1R01P), L will Latch
it and R will Release it.
8 –
DELAY BEFORE ACTION
Delay before the input changes into an active state when an out-of-limit condition occurs. Prevents glitches from
setting-off any alarms.
9 –
DELAY BEFORE RETURN TO NORMAL
Delay before the input returns to a normal state once an out-of-limit condition is over. Prevents too-brief returns-to-
normal from causing multiple repeated alarms.
10 –
ENABLE
Enable / disable the input. Useful to deactivate an input, without losing all its settings, when the input is causing
intermittent problems or nuisance alarms.
11 –
SYSTEM LOG
Log the input’s activity in the System Log. Useful when inputs do not need to be logged, but are required for day-
to-day operation.
12 –
QUALIFIER – STATE or DATA
13 –
MEASUREMENT UNIT
Select desired measurement unit, or enter your own. Maximum of 3 characters.
14 –
HYSTERESIS - HIGH LIMIT
Gap value which must be exceeded, when the input voltage returns from a high out-of-range state, before the input
can actually switch back to a normal state.
15 –
HYSTERESIS - LOW LIMIT
Gap value which must be exceeded, when the input voltage returns from a low out-of-range state, before the input
can actually switch back to a normal state.
16 –
SIGNALLING ON – ALARM
Enables / disables alarming. When checked, any out-of-limit condition will automatically generate an alarm. When
unchecked, no alarm will be triggered when an out-of-limit condition occurs.
17 -
SIGNALLING ON – RETURN TO NORMAL
Enables / disables
Return To Normal
signalling. When checked, a notification will be generated when the input
changes back to its normal state after an out-of-limit alarm condition. When unchecked, no notification will be sent
when the initial alarm condition returns to normal.
18 –
REFRESH / READ
Refresh / read the screen content.
19 –
SAVE / WRITE
Save the screen content.
20 –
EXIT
Exit menu.